background image

Multifunctional Wireless Panel

HDL-MP8B-RF.18

www.hdlautomation.com

User Manual

Summary of Contents for HDL-MP8B-RF.18

Page 1: ...Multifunctional Wireless Panel HDL MP8B RF 18 www hdlautomation com User Manual ...

Page 2: ...User Manual HDL MP8B RF 18 Multifunctional Wireless Panel User Manual Document updates Version Date Description V1 0 2015 09 05 Finish new document ...

Page 3: ...hange the button labels 4 6 Software Configuration 4 6 1 Basic Information 4 6 1 1 Wireless Setting via Mesh Gateway 4 6 1 2 Indicator Intensity 6 6 2 Key Assignation 6 6 2 1 Remark 6 6 2 2 Mode 7 6 2 3 Function 8 6 2 5 Key Lock 10 6 2 6 Key Status Setting 11 6 2 7 IR and Other Functions 11 6 2 8 Test the Switch 12 6 3 Channel Setting 12 6 4 Dimmer Setting 14 7 Online Upgrade 15 7 1 Automatic Upgr...

Page 4: ...Switch Universal switch Single channel lighting control Broadcast scene Broadcast channel Curtain Control GPRS Control Panel Control Security Module Z audio Control Universal Control Link Page DALI Area Dimmer RGB Control Logic Light Adjust Logic Scene etc The wireless power interface provides the working voltage And the panel can control four wireless power interfaces at the same time Built in te...

Page 5: ...amage this device 3 Technical Data Electric Parameters Working voltage DC5V from wireless power interface Power consumption 57mA DC5V Wireless transmit power 10dbm Wireless receive sensitivity 90dbm Indoor communication distance 30m barrier free RSSI receive signal intensity 80dbm Wireless central frequency WPAN China 780 to 786MHz SRD Europe 864 to 870MHz ISM North America 904 to 928MHz Default b...

Page 6: ... to 93 Approved CE RoHS Production Information Dimensions 86 86 10 5 mm Weight 110 5g Housing material Glass ABS PC Installation Wireless power interface EU wall box Protection degree IP20 4 Installation HDL MP8B RF 18 HDL MPWPI03 18 EU wall BOX Separation Use a screwdriver with 2 5mm insert to split gap pry up from position 1 to position 2 the wiring hole will open Then separate the panel and pow...

Page 7: ...side of plastic to the button 6 Finish to change the button label Notes Label dimension is 31 5mm X 14 5mm user can use same way to change each button label 6 Software Configuration 6 1 Basic Information 6 1 1 Wireless Setting via Mesh Gateway Before user can configure the wireless panel normally need to set the wireless parameters for it via mesh gateway and the mesh gateway needs to work in mesh...

Page 8: ...odule you will be able to change its ID and remark it the Subnet ID must be same as the gateway s 6 Click Modify Settings of Selection and it will show configurate successful then all its wireless parameters will follow the gateway s Band Frequency and PSK 7 Click all Node Exit Setup then the wireless devices will exit the wireless setup mode 8 Go to the HDL BUS setup tool s main interface to sear...

Page 9: ...ess of its LED indicators can be adjusted For this 4 touch buttons panel does not have LCD screen so no need to set the LCD backlight 6 2 Key Assignation The setting interface for the 8 buttons in HDL BUS Pro Setup Tool is shown in below screen shot 6 2 1 Remark Set the remark for each key for easy management ...

Page 10: ...ne target only one channel one scene one sequence etc Combination on Assign the Switch can turn on multiple targets channels scenes sequence etc Combination off Assign the Switch can turn off multiple targets channels scenes sequence etc Combination on off Assign the Switch can turn on off multiple targets channels scenes sequence etc Dblclick single switch Double click can control up to 49 target...

Page 11: ... targets Short long Jog Both short press and long Jog long press to turn on release to turn off can control up to 49 targets 6 2 3 Function Key type Scene Turn on off one scene Sequence Turn on off one sequence Timer switch Old command abandoned Single channel lighting control Turn on off one channel Curtain switch Control the curtain module stop open close GPRS control Send message out via SMS mo...

Page 12: ...ike changing the logic input conditions of e g 12in1 Sensor rather than using HDL BUS Pro Setup Tool this feature makes the system more flexible for end user For more info please refer to universal control command_ 12in1 xls download from ftp 59 41 255 150 HDL BUS HDL BUS 2Products Sensors SB CMS 12in1 Link page When such a button is pressed the DLP panel can jump to the designated page DALI Area ...

Page 13: ...solve the problem described below Key1 control combination on channel1 and 2 of dimmer go to 30 Key2 control combination on channel1 and 2 of dimmer go to 60 Key3 control combination on channel1 and 2 of dimmer go to 90 Press the key 1 and then key 2 and then key 3 now all LED indicators of the three keys are on the level of two channels is 90 If we set mutual exclusion for these three keys then t...

Page 14: ...rightness will go to 100 Memory save the brightness when turn on light the brightness will go to last brightness before turn off Dimming Valid enable dimming when long pressed Invalid Disable dimming just on off Keystroke status Valid Enable the LED indicator of the key Invalid Disable the LED indicator of the key 6 2 7 IR and Other Functions ...

Page 15: ...ou or maybe the load quality is not so good and trembles when at low level segment Long press time Set time for long press define the long press by end user Double click time Set time for double click define the double click by end user 6 2 8 Test the Switch Test the key function in the software equal to press the physical button 6 3 Channel Setting Each power interface has 3 output channels up to...

Page 16: ...hannel according to the real situation it is just like a remark would not affect the behavior of lamps Default selection Undefined Lower Limit If setup the lower limit for the channel when dimming to this value the output is 0 The Lower limit is useful if you unfortunately have some lamps which produce unstable trembling light when dimming in low segment You can bypass the unstable segment by sett...

Page 17: ...check to turn off it It s used to test the loads after installation 6 4 Dimmer Setting Dimmer Turnoff Temperature Set the temperature for protection when the panel s detected temperature reaches to the setting temperature it will turn off the connected loads automatically When the detected temperature is lower than the setting temperature it will restore the loads status again Dimmer brightness sa...

Page 18: ...nterface s address Channel no 1 3 is for address1 channel no 4 6 is for address2 channel no 7 9 is for address3 channel no 10 12 is for address4 7 Online Upgrade For the online upgrade there are two ways automatic upgrade and manual upgrade 7 1 Automatic Upgrade Upgrade steps 1 Select the online multi function wireless panel that you want to upgrade click Read Device Type to check its chip type ...

Page 19: ...nual 16 2 Select bin firmware click Add Device then it will be shown in the upgrade list 3 Click Upgrade Selected Device to start the upgrade 4 Upgrade finished 7 2 Manual Upgrade For manual upgrade the multi function wireless panel will enter the wireless setup mode ...

Page 20: ...es continuously to enter the wireless setup mode 2 Power off the multi function wireless panel then keep pressing the programming button the last two button when power on it it will enter the wireless setup mode and you will be able to read its ID in the Device line 3 Select bin firmware click Upgrade 4 Upgrade finished 5 Press the PROG button of wireless gateway 1 time to exit the wireless setup ...

Page 21: ...User Manual HDL MP8B RF 18 Multifunctional Wireless Panel User Manual 18 8 Note ...