Continuous output/HBM protocol (
Cont.out
)
WTX110
A4774-1.0
HBM: public
195
14
Continuous output/HBM protocol (
Cont.out
)
To access the
Cont. Out
group select the following keys:
Menu
Key
Function
Standard
Switch from
Standard
to version notice
WTX110V#.#
Display the current firmware version number
Call password entry within 3 seconds
Password
324
Enter the password
1 Service mode
Call
Service mode
Service:
Interface
Switch to the options of the
General
group
Service:
General
Switch between the subgroups of the
General
in
Service mode
The Ethernet (COM0) and COM1 ports can be configured as continuous
outputs. Various protocols can be set for them.
Assignment conflicts must be avoided when configuring the terminals.
The data set controlling remote indication consists of 15 ASCII characters plus
CR and LF. A fixed start character 'S,' a status character for rest (blank) or
motion (D), the net weight and the unit of measurement symbol are
transmitted. Unoccupied positions are filled by blanks.