65
PME-MP70DP
A0658-7.3 en
HBM
10.5 Parameterization with decimal and hexadecimal values
If you are using older parameterization tools, the parameter values have to be
converted into decimal or hexadecimal values:
Parameterization telegram
Octet Bits Parameter name
Possible values
Default
Meaning
0
0..7
reserved
0
4
do not change
1)
1-2
all
Diagnosis
0 = disabled
0xffff = enabled
enabled
External diagnosis
enabled
3
all
Data format
0 = 16‐bit integer
1 = 32‐bit integer
16‐bit integer
Defines the coding
format for the
measured values
4
Parameters for
module 1 to
module 8
dependent on
module type
1)
under certain circumstances, is automatically changed by your parameterization tool
Parameter input for modules MP30, MP55, MP60, MP01 and MP70:
Octet
(relat
ive)
Bits Parameter name
Possible values
Default
Meaning
0
0
Zeroing control
bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word
0
1
Taring control bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word
0
4
Clear Max store
control bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word
0
5
Clear Min store
control bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word
0
6
Hold Max store
control bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word
0
7
Hold Min store
control bit
0 = disabled
1 = enabled
disabled
enables functionality
for control via output
control word