SWIMMING  POOL  HEAT  PUMP UNIT

 

 

Installation & Instruction  Manual

 

 

 
 

Models  

HP50AEE 

HP70AEE

 

 

 

 

 
 

 
 

Hayward  Pool  Products Canada,  Inc.

 

2880 Plymouth Dr.,  Oakville, ON L6H  5R4

 

Haywardpool.ca / 1.888.238.7665

 

Summary of Contents for HP50AEE

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual Models HP50AEE HP70AEE Hayward Pool Products Canada Inc 2880 Plymouth Dr Oakville ON L6H 5R4 Haywardpool ca 1 888 238 7665 ...

Page 2: ......

Page 3: ...ol 5 3 4 Swimming Pool Heat Pumps Plumbing 6 3 5 Swimming Pool Heat Pumps Electrical Wiring 7 3 6 Initial Start up of the Unit 7 4 Usage and Operation 8 4 1 Color screen wire controller interface introduction 8 4 2 Color screen wire controller function introduction 10 4 3 Parameter list and breakdown table 15 5 Maintenance and Inspection 17 6 Appendix 18 6 1 Connection of PCB Illustration 18 6 2 W...

Page 4: ...according to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has foll...

Page 5: ...00 100 Fan Rotate Speed RPM 500 650 300 750 Fan Direction horizontal horizontal Noise dB A 43 53 42 57 Water Connection inch 1 5 1 5 Water Flow Volume m3 h gpm 4 1 18 5 6 2 27 3 Water Pressure Drop max kPa psi 4 3 0 62 4 9 0 71 Unit Net Dimensions L W H mm in 1048 442 770 41 2 17 4 30 3 1165 485 870 45 9 19 1 34 3 Unit Ship Dimensions L W H mm in 1130 460 780 44 5 18 1 30 7 1210 510 880 47 6 20 1 ...

Page 6: ...85 19 1 442 17 4 2 2 The dimensions for Swimming Pool Heat Pump Unit HP50AEE 1048 41 2 1002 39 4 water outlet 1 5 350 13 8 water inlet 1 5 104 4 1 610 24 0 unit mm in HP70AEE 102 4 0 water outlet 1 5 400 15 7 water inlet 1 5 1165 45 9 1115 43 9 815 32 0 3 ...

Page 7: ...sary spare parts for the water system that provided by users or the installer Attention Please follow these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is for referenc...

Page 8: ...r inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery Unit mm inch Air inlet Air outlet 3 3 How Close To Your Pool Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from the piping For the most part the piping is buried Therefor...

Page 9: ... at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 5 water may condense on the fins of the horseshoe shaped evaporator If the relative humidity is very high this could be as muc...

Page 10: ...3 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow these steps 1 Turn on your filter pump Check for water leaks and verify flow to and from the pool 2 Turn on the electrical power supply to the unit then press the key ON ...

Page 11: ... Booting status 5 Inlet water InlIe nlt etW wa a te te r r 20 5 OFF Time Temp Seting Outlet Water Time Te Hm ea p tin S g etS tin et g O O u u tt lle ett Water 07 00 28 5 18 5 4 1 2 Function interface Second interface 8 9 Third interface 12 13 M d Temp Setting Time Setting SET Silent Mode Silent Timing 10 11 14 15 8 ...

Page 12: ... icon will display when the compressor work 5 Lock icon The icon will display when the operation controller is locked 6 Fault icon The icon will display when the unit fails 7 Current Interface Slide left or right to switch the interface display 8 Mode Click to enter mode setting 9 Temp Setting Click to set the target temperature for current mode 10 Silent Mode Click to switch the silent mode 11 Si...

Page 13: ... the function selection Inl Ie nlt etW wa a te te r r 20 5 slide right Mode Temp Setting slide right Timer Time 07 00 Te Hm ea p tin S g etS tin et g O O u u ttlle et t Water 28 5 18 5 slide left SET Silent Mode Silent Timing slide left Parameter Main interface Second interface Third interface 4 2 3 Mode switch In the Second function interface click the Mode icon to enter into the Mode Setting int...

Page 14: ... Setting interface Slide up or down to select the DATE click to save and enter into time setting interface click to cancel and back to the prevoius interface In the time setting interface slide up or down to select TIME click OK to save and return to the Third function interface click back to the prevoius interface Time Settin ng click Time Setting 16 0 2017 slide up or down to select D M Y Time S...

Page 15: ...ming settings or slide it left to Deactivate the timing setttings click back to the third function interface click Time ON OFF 20 00 21 00 00 00 00 00 click the timer ON ON 19 20 00 click to quit 2 0 click to quit click to quit slide up or down to select the Start time OFF 20 21 00 click the timer OFF Time ON OFF 07 00 21 00 00 00 00 00 click OK to save ON 06 59 07 00 22 0 click to quit click to q...

Page 16: ...the Start time or End time slide the right round button to active or deactive the Silent Timing function Note ON OFF click SET Silent Timing ON OFF click the timer ON ON 2 Mode Temp Setting SET Silent Mode Silent Timing click to quit 20 00 23 00 click to quit 22 00 12 click back to the Third interface slide up or down click to quit slide up or down to select the Start time and click OK to save Sil...

Page 17: ...mp Sensor Fault 19 11 2018 05 20 P09 Antifreeze Temp Sensor Fault 19 11 2018 06 20 P09 Antifreeze Temp Sensor Fault 19 11 2018 07 20 1 10 Del click to page up click to page back Fault P07 Suction Temp Sensor Fault 14 05 2018 08 22 P02 Outlet Temp Sensor Fault 14 05 2018 09 22 2 10 Del 4 2 8 Keyboard locking In the Main interface press the button over 5 seconds the screen is locked press the button...

Page 18: ...4 USAGE 4 3 Parameter list and breakdown table 4 3 1Electronic control fault table 15 ...

Page 19: ...measurement Inv Sampling Volt F11 The input voltage sampling fault Checkand adjustthe current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Checkthe communicationconnection Input Over Cur F26 The equipment load is too large PFC fault F27 The PFC circuit protection ck the PFC switch tube short circuit not IPM Over heating F15 The IPM module is overheat Checkand adjustthe current measur...

Page 20: ...he unit should be dry clean and well ventilated Clean the side heating exchanger regularly to maintain good heat exchange as conserve energy The operation pressure of the refrigerant system should only be serviced by a certified technician Check the power supply and cable connection often Should the unit begin to operate abnormally switch it off and contact the qualified technician Discharge all w...

Page 21: ...Sign Meaning V 12V power R No use T No use A 485A B 485B G GND power 6 1 Connection of PCB illustration 1 Wire control interface diagram and definition V R T A B G 2 Controller interface diagram and definition 18 ...

Page 22: ...tput temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch coil 2 temperature input 18 AI DI11 Master slave machine switch Antifreeze temperature input 19 AI12 50K System Exhaust temperature input 20 0_5V_IN Compressor current detection Pressure sensor input 21 PWM_IN Master slave machine switch Feedback signal of EC fan input 22...

Page 23: ...1 7 K2 KM1 BLK WHT Y G L1 L2 1 2 TO POWER TO PUMP 4V PC1002 RLY1 CN2 GND 485B1 485A1 12V GND YEL BLK 3 RED BLK YEL Y G SUPPLY 208 230V 60Hz 240V CN9 CN8 485B2 485A2 12V WHT 4 RED CON1 AT Ambient temperature COMP Compressor CT Coil temperature EP Exhaust protection EEV Electronic expand valve ET Exhaust temperature FM Fan motor FS Flow switch HP11 High pressure protection 4 0MPa HP12 High pressure ...

Page 24: ...ed View HP50AEE 1 Complete machine structure explosion diagram 9 10 11 8 7 6 5 12 13 14 15 16 4 17 18 19 3 2 1 31 30 29 28 27 26 25 24 23 22 21 20 2 Electrical control structure explosion diagram 32 33 34 35 36 39 38 37 21 ...

Page 25: ...1070 20120022 Chassis assembly Galvanized sheet 1 20 20000 360005 Flow switch PSL 1 3 4 1 21 20000 360157 Pressure Switch 0 30MPa 0 15MPa 0 05 normally open 1 22 2001 3605 Pressure Switch 3 2MPa 4 4MPa 0 15 normally closed 1 23 20000 360059 Pressure Switch 3 2MPa 4 0MPa 0 15 normally closed 1 24 20000 360157 Needle valve 40mm 1 2 T0305 10 2 25 2000 1460 Three links 6 5 2x 6 5 T x0 75 T2M 2 26 3040...

Page 26: ...oded View HP70AEE 1 Complete machine structure explosion diagram 9 10 11 7 12 6 13 5 14 15 16 17 3 2 1 18 30 29 28 27 26 25 24 23 22 21 20 19 2 Electrical control structure explosion diagram 31 33 34 41 40 39 38 23 37 36 35 ...

Page 27: ...T x0 75 T2M 1 20 304030 00000002 Three links 40mm 1 2 T0305 10 1 21 20000 140150 Needle valve 9 52 2x 6 35 T x1 0 1 22 20000 140572 Electronic expansion valve DPF B 2 0C 008 1 23 20000 360157 Pressure Switch 0 30MPa 0 15MPa 0 05 normally open 1 24 2001 3605 Pressure Switch 3 2MPa 4 4MPa 0 15 normally closed 1 25 20000 360059 Pressure Switch 3 2MPa 4 0MPa 0 15 normally closed 1 26 2004 1444 Filter ...