background image

 

Page 7 

2. The 

Vacuum 

switch. For the stove to 

operate correctly the firebox needs to be 
sealed. During the first 30 seconds after the 
stove has been turned on the control board 
will check to see if the switch senses negative 
pressure in the stove. If there is no negative 
pressure, the stove will go into “Safety 
shutdown”. Once the stove completes the 
safety shutdown the #2 LED will start 
blinking. 
 

Safety Features 

 
1.  

”High Limit” switch”,

 an overheat safety 

switch will shut off the fuel feed if the stove 
reaches a temperature above normal 
operating temperature. This is a 

manual 

reset

 High Limit switch. There is no 

diagnostic light associated with this switch. 
When this switch shuts the stove down the 
control board will be in 

“Internal Alarm”

Eventually the P.O.F. switch drops out and 
the #3 LED will start blinking. The switch 
will need to be manually reset. For this 
reason it would be sensible to check this 
switch first any time the #3 diagnostic LED 
is blinking. When the High limit switch 
causes a shutdown, the problem in the stove 

must

 be diagnosed before the stove is put 

back in service, (Defective room fan, dirty 
room fan, defective high limit switch or 
possibly a bad control board) 
 
2.   

Proof of Fire switch

 also called the 

P.O.F.

 This senses the temperature rise in the 

exhaust system. The switch is normally open 
and closes the circuit at 110 degrees. The 
stove will shut down if temperatures above 
110 degrees F are not sensed during start up 
or drop below 110 degrees during normal 
operation. 
 
3. 

Vacuum switch 

also called the

 Negative 

pressure switch

. When the stove is turned on 

the exhaust fan will create a negative 
pressure in the firebox. The control board 
continually checks to see if negative pressure 

is present during operation of the stove. If the 
exhaust venting system becomes clogged or 
obstructed, the firebox door or ash pan door are 
left open or the exhaust fan quits working the 
control board will go into “Safety shutdown”. 
There is a 90 second window to allow for 
cleaning the glass and emptying the ashpan 
before then stove shuts down. This is sufficient 
for the daily maintenance. 
 

The St. Croix pellets stove has been Safety 
Tested by an accredited, independent 
laboratory. 

 
Shutting The Stove Off (Refer Figure 2) 

 
1. Press the ON/OFF switch (2) to turn off the 
auger feed system; the fire will go out in a few 
minutes. 
 
2. The Room Air Fan and the Combustion 
Exhaust Fan will continue to run until the P.O.F. 
switch drops out. Meanwhile the Self-Cleaning 
Grate continues to run at normal operating 
speed. When the P.O.F. switch drops out the 
Room Air Fan, Combustion Exhaust Fan and 
the Self-Cleaning Grate Motor will turn off.  
 

3. NEVER unplug the stove to shut it off. 
Doing so may cause a significant amount of 
smoke to enter the room. 

 

 

 
 

 
 
 
 

WARNING: These safety features are
designed to protect life and property.
Bypassing these features voids all warranties
and the safety listing of the stove. 

Summary of Contents for 45Lbs. Hopper

Page 1: ...ustment 4 Pre Lighting Instructions 5 Lighting Your Stove 6 Diagnostic Features 6 Shutting the Stove Off 7 Safety Features 7 MAINTAINING THE STOVE 8 Daily Maintenance 8 Periodic Maintenance 9 Yearly Maintenance 11 REMOVABLE HANDLE TOOL 11 SAFE OPERATION 12 TROUBLESHOOTING 12 CAST IRON PANEL REMOVAL 13 ELECTRICAL LAYOUT 14 MULTI FUEL USE ADD CORN TO THE MIX 14 WARRANTY 15 Your Dealer Is 403 ...

Page 2: ...pended to ensure that each St Croix wood pellet stove meets the highest quality standards of material and workmanship Here are some important aspects of wood pellet stove installation and operation which you must observe in order to obtain maximum comfort and safety from your new St Croix wood pellet stove 1 Have your new St Croix wood pellet stove installed by trained qualified personnel 2 Use on...

Page 3: ...arge Viewing Glass Digital Control Board With Diagnostic Features Exclusive SmartStat Fully Automatic Auto Ignite System Hinged Front Panel For Easy Access To the Firepot Area 45 LBS HOPPER Tube Scraper Rod Ash Clean out Rod Large Ash Pan with Quick Release Latches ...

Page 4: ...ast once every two months during the heating season to determine if a creosote build up has occurred If a significant layer of creosote has accumulated 3 mm or more it should be removed to reduce the risk of a chimney fire Use of an appropriately sized chimney brush or the services of a professional chimney sweep are recommended SATISFACTORY PERFORMANCE The keys to satisfactory performance are pro...

Page 5: ...t fans and icing of air vents can adversely affect proper stove operation 10 Smoke detectors installed in the same general area as the stove may be activated if the stove door is left open and smoke is allowed to enter the area Combustion Damper Adjustment Your stove is equipped with an air inlet damper Before lighting your stove for the first time READ the following and adjust this damper accordi...

Page 6: ... to work The buttons on the board function as follows Refer to Figure 2 The touch pad buttons are labeled with the white numbers 1 through 5 Figure 2 Control Box 1 The heat advance button 1 will advance the setting between level 1 and 5 Once you reach level 5 it will drop back to level 1 Each level has a LED light to indicate where the board is set 2 The On Off button 2 turns the stove on and also...

Page 7: ...ing for 5 minutes e The board will check for P O F again If the board still fails to sense the Proof of Fire switch the stove will go into Safety shutdown See section on Diagnostic Features on page 6 If this happens repeat steps 1 through 4 from the section on Lighting Your Stove CAUTION NEVER ADD FIRE STARTER TO A HOT STOVE Damper Adjustment Refer to Figure 1 Once the stove has been lit for the f...

Page 8: ...rees The stove will shut down if temperatures above 110 degrees F are not sensed during start up or drop below 110 degrees during normal operation 3 Vacuum switch also called the Negative pressure switch When the stove is turned on the exhaust fan will create a negative pressure in the firebox The control board continually checks to see if negative pressure is present during operation of the stove...

Page 9: ...ged Clean as needed With proper precautions the grate may be partially cleaned while the stove is hot Follow these steps CAUTION THE DOOR AND FRONT PART OF THE STOVE WILL BE HOT DO NOT TOUCH ANY PART OF THE STOVE THAT IS HOT a Wear a leather glove that covers the lower arm b Turn the auger feed system OFF and allow the flame to subside to glowing coals c Open the firebox door slowly to prevent dra...

Page 10: ...he rate of burn and the quality of fuel will determine how often the window needs cleaning Prolonged burning at a slow burn rate will result in the need for more frequent window cleaning Burning poor fuel also increases the need to clean the window Cooling the stove and wiping the window daily with a cloth or paper towel will normally keep the window from accumulating difficult to clean residue Us...

Page 11: ...the keyhole slots and the back of the baffle is lifted up over the inner back 5 Periodic cleaning of the exhaust system is required Under certain conditions creosote buildup may occur rapidly Low quality pellets and poor installations require more frequent chimney cleanings See Page 3 Preventing Chimney Fires The products of combustion will also contain small particles of fly ash The fly ash will ...

Page 12: ... become disconnected call your dealer for service 5 The exhaust fan should be removed and cleaned annually Call dealer for this service Annual oiling of the motors is not needed 6 Fall Startup Prior to lighting the first fire check the outside area around the exhaust and air intake systems for obstructions Try all controls to see that they are working prior to lighting a fire 7 The Versa Grate Sys...

Page 13: ...ct the flow of flue gases Incomplete combustion such as occurs during start up and shut down or incorrect operation of the room heater will lead to some soot formation which will collect in the venting system The exhaust system should be inspected at least once a year to determine if cleaning is necessary Check more frequently at first to determine a schedule for cleaning the venting system based ...

Page 14: ...uts and bolts After removing the bolts the sides slide back and can be removed Once both sides have been removed you have access to the Versa grate and Igniter wires on the right hand side The Combustion fan Vacuum switch High limit switch and the P O F switch can be found on the left side There is no need to remove the cast iron panels to access the Convection fan Wiring connections can be reache...

Page 15: ... Harness 11 80P20296 Versa Grate Motor Figure 10 MULTI FUEL USE ADD CORN TO THE MIX The Hastings is now approved to burn a mixture of pellets and corn maximum 50 corn Operation of the stove doesn t change burning a mixture of pellets and corn The burn pot will need to be cleaned on a daily basis using the Pot Scraper Tool shown in figure 3 on page 8 Use the Pot Scraper Tool to remove any clinkers ...

Page 16: ...ty have been met the manufacturer s total responsibilities and liabilities shall be to repair or replace at the manufacturer s option the defective part s All costs of removal shipment to and from the dealer or manufacturer any losses during shipment and reinstallation and any other losses due to the stove being removed shall be covered by the owner of the stove NEITHER THE MANUFACTURER NOR THE SU...

Page 17: ...Page 16 Even Temp Inc P O Box 127 Waco NE 68460 EMAIL SUPPORT EVENTEMPINC COM WEB ADDRESS www eventempinc com ...

Reviews: