9 Block BASIC FUNCTION
Device Functions Proline Promag 55
124
Hauser
POSITIVE ZERO RETURN
(6605)
Use this function to interrupt evaluation of measured variables. This is necessary when a
piping system is being cleaned, for example. This setting acts on all function and outputs
of the measuring device.
Options:
OFF
ON
→
Signal output is set to the "ZERO FLOW" value.
Factory setting:
OFF
SPECIAL FILTER
(6606)
There is the option of activating two signal filters in this function. These filters make it
possible to either suppress the signal caused by severely fluctuating flows (selection
"STANDARD") or to reproduce it completely – both on the display and at the signal
outputs (selection "DYNAMIC FLOW").
Options:
STANDARD
For signal output with normal, stable flow.
DYNAMIC FLOW
For signal output with severely fluctuating or pulsating flow.
Factory setting:
STANDARD
"
Caution!
• The signal behavior at the outputs also depends on the SYSTEM DAMPING function
(6603).
• Additional filter settings (e.g. STANDARD CIP or DYNAMIC FLOW CIP) can only be
selected using a special service code. Such settings that are mostly made by a service
technician are deleted again if the customer code is entered anew and can then no
longer be activated.
Function description
BASIC FUNCTION
➞
SYSTEM PARAMETER
➞
CONFIGURATION
Summary of Contents for Proline Promag 55
Page 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Page 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Page 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Page 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...