8 Block INPUTS
Device Functions Proline Promag 55
108
Hauser
8.2
Group CURRENT INPUT
8.2.1
Function group CONFIGURATION
INPUTS
F
⇒
STATUS INPUT
FAA
⇓
CURRENT INPUT
FCA
⇒
CONFIGURATION
520
Function description
INPUTS
➞
CURRENT INPUT
➞
CONFIGURATION
ASSIGN CURRENT
(5200)
Use this function to assign a process variable to the current input.
Options:
OFF
TEMPERATURE
DENSITY
Factory setting:
OFF
CURRENT SPAN
(5201)
Use this function to define the current span. This selection defines the operational range
and the upper and lower signal on alarm.
Options:
0–20 mA
4–20 mA
4–20 mA NAMUR
4–20 mA US
0–20 mA (25 mA)
4–20 mA (25 mA)
Factory setting:
4–20 mA NAMUR
!
Note!
When switching the hardware from an active (factory setting) to a passive output signal,
select a current span of 4 to 20 mA (see Operating Instructions Promag 55, BA119D/06).
Current span / operational range (measuring information):
0–20 mA / 0 to 20.5 mA
4–20 mA / 4 to 20.5 mA
4–20 mA NAMUR / 3.8 to 20.5 mA
4–20 mA US / 3.9 to 20.8 mA
0–20 mA (25 mA) / 0 to 24 mA
4–20 mA (25 mA) / 4 to 24 mA
VALUE 0_4 mA
(5202)
Use this function to assign a value to the 0/4 mA current.
User input:
5-digit floating-point number
Factory setting:
Dependent on the process variable assigned to the current input (see function
ASSIGN CURRENT, 5200).
– Density: 0.5 kg/l
– Temperature: –50 °C
!
Note!
The appropriate unit is taken from the functions UNIT DENSITY (0420) or
UNIT TEMPERATURE (0422).
Summary of Contents for Proline Promag 55
Page 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Page 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Page 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Page 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...