Chapter 3: Operation
Recalling Default Parameter Settings
Table 3-9 "Parameter Options—B2/C2 Modules"
describes
all of the parameter settings for the HMX6801
+
B2/C2 and
HMX6801
+
B4/C4 modules, including the original factory defaults. To
return this module to its default settings, you can either reset each
parameter individually, or do a global recall following this procedure:
1. Rotate the hex switch to “0.”
2. Toggle the navigation switch to the bank number “0.”
Use the control LEDs to verify which bank you have selected, or
use an available 6800
+
software control option (serial/local or
Ethernet/remote) to aid in confirming your bank selection.
3. Rotate the hex switch to the global recall parameter “F
.
”
4. Toggle the navigation switch to “On.”
Use an available 6800
+
software control option to aid in viewing,
setting, and confirming the parameter value.
Reading Software and Hardware Versions
The current software and hardware version of your HMX6801
+
B2/C2
and HMX6801
+
B4/C4 module can only be viewed using a
CCS-enabled control panel or a CCS software application, such as Pilot
or
+
Pilot Lite. See your
NUCLEUS Network Control Panel,
LCP-3901-1U and RCP-CCS-1U Local, and Remote Control Panel
Installation and Operation Manuals
,
CCS software application user
manual
,
or CCS software application online help for information on
viewing software and hardware version numbers.