T U N I N G / C O N T R O L M E N U
K ( I N T G. ) 2 6
K ( P R O P. ) 2 . 0
K ( D E R V. ) 5 2
Chapter 6 - Setup
6-17
FIG. 6-13 ENTERING CALCULATED CONSTANT VALUES
Step 9. Press the Clear button to set the value to 0.
Step 10. Press the down arrow
↓
button to go to the next constant K(p).
Clear the old value and enter the K(p) calculated value.
Step 11. Press the Enter button to accept the new K(p) value.
Step 12. Press the down arrow
↓
button to go to the next constant K(d).
Clear the old value and enter the K(d) calculated value.
Step 13. Press the Enter button to accept the new K(d) value.
Step 14. Press the down arrow
↓
button until the cursor is to the left of
the REC LEVEL Sub-Menu.
Step 15. Initially change the REC LEVEl to 2.0.
Step 16. Press the Enter button to accept the REC setting.
Step 17. Press the Exit button twice to get to the operational display.
Manual Tuning
Control Process
(Cont’d)
Step 1. Make sure the feeder is on.
Step 2. Press the Set Pt button.
Step 3. Enter the Security code number.
Step 4. Press the Enter button. The Set Point Menu appears with the
cursor to the left of the RATE Sub-Menu.
Step 5. If the Rate display shows “MANUAL” or “REMOTE”, press
the Select button to select the Value display.
Step 6. Press the Clear button to clear the values.
Step 7. Use the numeric keys to enter the new flow rate.
NOTE:
Enter a flow rate that will be used in the application.
Step 8. Press the Enter button to accept the new rate.
Step 9. Press the Exit button to return to the operating display.
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...