T U N I N G / C O N T R O L M E N U
A V R G. ( 1 - 2 0 0 ) 1
R E C L E V E L 0 . 0
R E C T I M E ( S E C ) 3 . 0
HI 2160RC
PLUS
MANUAL
6-14
FIG. 6-11 SETTING THE AVRG AND REC LEVELS
Step 7. Press the Clear button to clear the AVRG. value.
NOTE:
When you enter a value that is less than three digits, a zero appears before the digit
entered (e.g. 002, 014). When you press the down arrow button to move to the next
Sub-Menu the zero(s) disappear (e.g. 2, 14).
Step 8. Press the Enter button to accept the new value.
Step 9. Press the down arrow
↓
until the cursor appears to the left of
the REC LEVEL Sub-Menu.
Step 10. Press the Clear button to clear the REC LEVEL value.
Step 11. Use the numeric keys to enter 0.0. Entering 0.0 prevents
alarms during the data gathering procedures.
Step 12. Press the Enter button to accept the 0.0 value.
Step 13. Press Exit twice to get to the Operations Display.
Step 14. Press the Set Pt button. The security message displays.
Step 15. Enter the HI security code number.
Step 16. Press the Enter button. The Set Point Sub-Menu appears.
Step 17. With the cursor next to RATE, press the Select button until
MANUAL appears.
Step 18. Press the Enter button to accept the MANUAL selection.
Step 19. With the cursor next to AMOUNT, press the Select button
until CONTINUOUS appears.
Step 20. Press the Enter button to accept the CONTINUOUS selection.
Step 21. The controller is now in the MANUAL operating mode.
Step 22. Press the Exit button to return to the Operations Display.
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...