Chapter 4 - Setup
4-7
On some PLC platforms it may be necessary to enter
the Vendor ID, the Product Type, the Product Code,
Input/Output Words and Extra Data Length. See
below:
•
HARDY_VENDOR_ID 0x102 (258 decimal)
•
HARDY_PRODUCT_TYPE 0x54 (100 decimal)
•
HARDY_PRODUCT-CODE 5
•
Input Words - 32
•
Output Words - 32
•
Extra Data Length - 0 for Firmware REV A or 48
for later Firmware REVs.
Step 6.
Click on the “Apply.” button.
Step 7.
“OTHER” appears under the Part # col-
umn heading. (See Fig. 4-8)
FIG. 4-8 I/O CONFIGURATION DIALOG BOX
Step 8.
The HI 1769-WS I/O is configured and
ready to communicate with the
MicroLogix 1500 Processor.
Configuring the
HI 1769-WS in
RSLogix 5000 for
CompactLogix
To set up communication between the CompactLogix
Processor and the Weigh Scale Module you will need
to do the following in RSLogix 5000:
Step 1.
Click on the + next to I/O Configuration.
(See Fig. 4-9).