Chapter 4 - Setup
4-7
FIG. 4-2 PRIMARY AND REMOTE
COMMUNICATION DIAGRAM
Command Word
Encoding
You may write up to 7 words at a time to either the
Logical O file or the Logical M0 file. Word #0 of the
8 word output file is used to specify where words 1-7
go in either the logical O or M0 file, is called the
“Command Word”. Word #0 of the I file will always
be a copy of the “Command Word”.
Bits 15 & 14
11 = write 0 to 7 words to the logical M0 file, Read 7
words from the M1 file.
NOTE:
You need to run any command through M files before
previous writes take effect.
01 = write 0 to 7 words to the logical O file, Read
(configured) I
10 = configure 0 to 7 words for the I file return, con-
figure 7 words to read from Logical I file.
00 = the configured I file returned.
Bits 8-13
Number of words to write to the logical M0 or logical
O file.
Bits 0-7
Offset (in words) in the logical M0 or logical O file
where the write begins.
Command Word - 16 bits
Bits 15-14
Bits 13-8
Bits 7-0
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...