HI 1746-WS WEIGH SCALE MODULE
3-8
cation requires load cells cables that are less than 50
ft. you must leave the jumpers installed or connect the
sense lines, one or the other. If your application calls
for load cell cables over 50 ft. or you are using C2
load cells, remove the jumpers and connect the sense
lines. The jumpers or sense lines must be installed at
all times.
WARNING: Load cell cable length has been calcu-
lated into C2 calibration data. Hardy recommends
that you DO NOT CUT your Advantage or Advantage
Lite load sensor cable, as your C2 accuracy will be
affected and the warranty will be voided.
Industry Standard
Load Cells
FIG. 3-7 INDUSTRY STANDARD LOAD CELLS
WIRING DIAGRAM