HI 1756-WS WEIGH SCALE MODULE
4-12
Reply data contains 3 fields
• Command (DINT): The command number
• Channel (DINT): The channel number
• Status (DINT): Status information
NOTE:
Some commands will produce longer replies.
Zero Command
(ZEROCMD)
The Zero Command requests that the current gross
weight be set to zero.
Command Number: 1 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8
Error Return Values:
• OUTOFTOLERANCE - the current weight
value is beyond the limits set by the zero toler-
ance parameter.
NOTE:
The amount of weight zeroed off is cumulative. The
Autozero command will fail if the current gross weight
plus any previously zeroed amount exceeds the zero
tolerance value.
• “STATUSWORD” - the command failed
because either the weight was not stable (in
motion) or there was some kind of A/D error.
Tare Command
(TARECMD)
The Tare Command requests the current net weight be
set to zero.
Command Number: 2 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8
Error Return Values:
• “STATUSWORD” - the command failed
because either the weight was not stable (in
motion) or there was some kind of A/D error.
Summary of Contents for A Series
Page 14: ...HI 1756 WS WEIGH SCALE MODULE 1 6 ...
Page 28: ...HI 1756 WS WEIGH SCALE MODULE 3 10 ...
Page 52: ...HI 1756 WS WEIGH SCALE MODULE 4 24 ...
Page 62: ...HI 1756 WS WEIGH SCALE MODULE 6 2 FIG 6 2 DISCRETE DATA ...
Page 72: ...HI 1756 WS MANUAL 7 10 ...
Page 80: ...HI 1756 WS MANUAL Write Parameters WRITEPARAM 4 18 Z Zero Command ZEROCMD 4 12 ...