
5 - Operation
5. 2
Adjusting Pressure equalisation
Pressure equalisation on machines fitted with HARDI EVC or
Braglia CB/2 control units are adjusted using these steps;
•
With the boom section valves open, run the sprayer at normal
average spraying pressure.
•
Note the reading on the pressure gauge (B)
•
Close the first section valve (1) by turning off at the
switchbox.
•
When system pressure has stabilised, adjust the first
equalisation valve (A) until the original spraying pressure is
restored, then reopen the valve at switchbox.
•
Repeat the procedure until both valves have been balanced.
μ
Attention: After service procedures it is recommended to re-
calibrate equipment before spraying. The equalisation procedure
is generally only required after servicing, changing nozzle size or
when compensating for worn nozzles.
Summary of Contents for Mercury Covamax series
Page 1: ...MERCURY COVAMAX Operator Instruction Manual 67002404 100 HAU 08 2009 www hardi com au...
Page 10: ...Table of Contents TOC 8...
Page 18: ...2 Safety 2 6...
Page 88: ...6 Maintenance 1 18 Maintenance Activity Record Date Service Performed...
Page 92: ...7 Fault Finding 1 4...
Page 100: ...8 Technical Specifications 8 8...