WARNING
CAUTION
Board Type Digital Temperature Controller
BX8
Thank you for purchasing Hanyoung Nux products. Please read the instruction
manual carefully before using this product, and use the product correctly.
Also, please keep this instruction manual where you can view it any time.
INSTRUCTION MANUAL
▍Safety information
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or property damage
Please read the safety information carefully before the use, and use the product correctly.
The alerts declared in the manual are classified into
Danger, Warning
and
Caution
according to their importance
The input/output terminals are subject to electric shock risk. Never let the input/output terminals come in contact
with your body or conductive substances.
DANGER
MA0204KE211029
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hanyoungnux.com
HANYOUNGNUX CO.,LTD
•The contents of this manual may be changed without prior notification.
•Any use of the product other than those specified by the
manufacturer may result in personal injury or property damage.
•If there is a possibility that a malfunction or abnormality of
this product may lead to a serious accident, install an
appropriate protection circuit on the outside and plan for
preventing accidents.
•Since this product is not equipped with a power switch and fuse,
install them separately on the outside (fuse rating: 250 VAC 0.5 A).
•Please supply the rated power voltage, in order to prevent
product breakdowns or malfunctions.
•To prevent electric shocks and malfunctions, do not supply
the power until the wiring is completed.
•The product does not have an explosion-proof structure,
so avoid using it in places with flammable or explosive gases.
•Never disassemble, modify, process, improve or repair this product,
as it may cause abnormal operations, electric shocks or fires.
•Do not touch the terminals to avoid electrical shock or malfunction.
•Please disassemble the product after turning OFF the power.
Failure to do so may result in electric shocks, product
abnormal operations or malfunctions.
•We recommend regular maintenance for the continuous
safe use of this product.Some components of this product
may have a lifespan or deteriorate over time.
•The warranty period of this product, is 1 year, including its
accessories, under normal conditions of use.
•The ambient temperature exceeds 0 ~ 50 ℃
•The ambient humidity exceeds 20 ~ 90 % RH.
•Places where temperature changes suddenly or condensation occurs.
•Places exposed to corrosive gases
(especially harmful gases, ammonia, etc.) or flammable gases.
•Places where vibrations and impacts are applied directly
to the product body.
•Places with liquids, oils, chemicals, steams, sunlight.
•Places with a lot of dirt, dust, salt, iron.
•Places where large inductive disturbance, static electricity,
magnetic noise can be generated easily.
•Places where heat accumulation occurs due to radiant heat, etc.
•This controller does not have outer case and is only
composed of PCB (printed circuit board)so you need special
attention when you install it to panel. Especially, when
insulated against iron plate, and oil or water leak inside the
panel, there is danger of fire, so inspection is required.
•Use the predetermined compensating cable with thermocouple.
•For RTD input use a cable with small lead wire resistance
and without resistance difference among 3 wires.
•To avoid the inductive noise influence, separate input signal
wires from the power and load wires.
•Keep input wires away from output signal wires and
be sure to use shielded wires to ground.
•In places with a lot of noise, use the following procedure:
connect a surge absorber to the connector coil side if the magnet
connectors are connected to the relay contact output load.
•When there is a lot of noise from the power, we recommend
to use insulation transformer and noise filter. Please install
the noise filter to a grounded panel or structure, etc. and
make the wiring of noise filter output and product
power supply terminals as short as possible.
•The product power cables are effective when twisted and connected
(tightly twisting the power cables is effective against noise)
•For the heater break alarm, the heater power supply and the
controller power supply should be connected using the
same power cables when a heater break alarm.
•The preparation period of the contact output is required
during power supply. If used as a signal to external interlock
circuit, etc. please use a delay relay together.
•Be careful during wiring, as this product has a narrower
distance among terminals, compared with other products.
•As the connection between the main board and the display
board of this product is a signal line,please install after
taking into consideration the insulation relationships,
so that there is not noise influence.
•If the operation frequency such as proportional operation is
high, connecting the load with the output relay rating without
room will shorten the service life, so use an extra relay.
In this case,SSR output type is recommended.
·When using electromagnetic switch: the proportional cycle
is at least 30 seconds
·When using SSR: he proportional cycle is at least 1 second
·Contact output life : Mechanical: min. 10 million times (no load)
Electrical: min. 100 thousand times (rated load)
•SSR/current output: not electrically insulated from internal circuit.
•If the alarm function is not set correctly, it will not be output in
case of abnormal operation,so please check it before operation.
•When the input (sensor) is disconnected, “b.out”
will be displayed on PV display. When replacing the sensor,
be sure to turn off the powery.
▍
Suffix code
Model
Code
Information
BX8-
⃞ ⃞ 48×48 ㎜ Board Type Digital Temperature Controller
Control Type 0
Normal Type
1
Heating/Cooling
Optional
0 SV2/SV3
1 HBA
2 RS485
3 HBA/RS485
■ Input
▍
Specification
Input
Thermocouple: K, J, E, T, R, B, S, L, N, U, WRe 5-26, PL-Ⅱ
RTD : Pt100 Ω, KPt100 Ω.
Direct voltage : 1 - 5 V, -10 - 20 ㎷, 0 - 100 ㎷ (free scale)
Sampling cycle 250 ㎳
Input resolution Below decimal point of measurement range
Input impedance Thermocouple and mV input: min. 1 ㏁, DC V: 1 ㏁
Allowable signal
source resistance Thermocouple : max. 250 Ω, Voltage : max. 2 kΩ
Lead wire tolerable
resistance
RTD: max. 10 Ω / 1 wire (but the conductor resistance among 3 wires should be the same)
Input tolerable voltage within ±10 V (T/C, RTD, Voltage : mV DC), ±20 V (Voltage : VDC)
Noise removal rate NMRR (Normal mode) : min. 40 dB (50/60 ㎐ ±1 %)
CMRR (Common mode) : min. 120 dB (50/60 ㎐ ±1 %)
Standard
T/C, RTD : KS, IEC, DIN
Standard junction temp.
compensation tolerance ±1.5 ℃ (15 ~ 35 ℃), ±2.0 ℃ (0 ~ 50 ℃)
BURN-OUT
T/C: OFF, UP/DOWN scale selectable. RTD : UP Scale
(detection current at thermocouple and RTD BURN-OUT: approx. 50 nA)
Accuracy
±0.5 % (FULL SCALE)
Input range
T/C and RTD are changeable within range of input signal and measurement range.
DC voltage: min. voltage and max. voltage are changeable within each measurement range.
Scaling available in the measurement range conditions
■ Output
Retransmission
output
·Resolution : Approx. 3,000 ·Sampling cycle : 250 ㎳
·Accuracy : ±0.5 % of max. scale (4 - 20 ㎃ range)
Alarm output
·Contact: 1a
·Point: 1 point
·Output points: Refer to “Terminal Arrangement”
Control
output
Relay
contact
output
·Time resolution : 0.1 % or 10 ms (the smaller)
·Proportional cycle : 1 ~ 1000 sec.
·Output operation : time proportional, ON/OFF
·Output limit : 0.0~100.0 % range, high limit(OH) or low limit(OL) (selectable also during AT)
·ON/OFF hysteresis : 0 ~ 100 % (Full scale)
Control
output
SSR voltage
pulse output
·Proportional cycle: 1 ~ 1,000 sec.
·OFF voltage: max. 0.1 V d.c.
·Output operation: time proportional
·Time resolution: 0.1 % or 10 ms (the smaller)
·Output limit: 0.0~100.0 % range, high limit (OH) low limit(OL) (selectable also during AT)
Current
output
(4-20 mA)
·Sampling time : 250 ms·Output operation : PID control
·Accuracy : ±0.5 % of full scale (4 - 20 mA range), Resolution : Approx. 3,000l
·Output ripple : max. 0.3 % (P-P) of max. scale (150 Hz)
·Output limit : -5.0 ~ 105.0 % range, high limit(OH) or low limit(OL) selectable also during AT)
▍
Function
※ Output type can be selected from relay, current or SSR, and heating/cooling types can be set individually
Measurement
input
·Input correction (Bias) : -100.0 ~ 100.0 % for instrument range
(desired correction value can be compensated for measured input value)
·Scaling : The measurement range can be scaled according to the setting of the maximum
measurement range (SL-H) and minimum
·measurement range (SL-L). Filter : OFF, 1 ~ 120 sec.
Control
·Number of PIDs per set value (SV): you can set up to 3 types of set values (SV) and select PID constants for each
·Auto-tuning : According to set value (Standard type, Low PV type)
·Proportional Band : 0.1 ~ 999.9 % (Max. range), 0.0 ~ 999.9 % (During heating - cooling control)
·Integral Time : OFF, 1 ~ 6000 sec. ·Derivative Time : OFF, 1 ~ 6000 sec.
·ON/OFF control : By selecting output code (OT) “0”
·PID selection : Zone PID/Auto 1, 2, 3 selectable
·Manual Reset : -5.0 ~ 105.0 % of output (valid when I=OFF)
·Direct / Reverse action : Changeable by parameter
·Emergency output value : -5.0 ~ 105.0 % of output value (normal type), 0.0~105.0 % (heating/cooling type)
·ON/OFF hysteresis (HYS) : 0.0 ~ 100.0 % of instrument range (valid when ON/OFF control is set)
·Heating/cooling dead band: -100.0 to 50.0% about output value
·Heating-Cooling hysteresis : -100.0 ~ 50.0 % of output value
·ARW (Anti Reset Wind-up) : AUTO, 50.0 ~ 200.0 %
·Fuzzy : ON/OFF selection by parameter
·Ramp: It is possible to set rising temperature and falling temperature gradients in hours or minutes when power is ON.
Retransmission
output
·Transmission signal: process value (PV), set value (SV), output value (MV) selectable.
Sensor power supply (SPS) 24 V d.c.
·Continuous output (However, when retransmission output is used, the sensor power can not be used)
·Scaling: Indication value, set value
Alarm output
·Set point: depends on specifications of each model (refer to connection diagram)
·Alarm types : High/Low process alarm, High/Low deviation alarm, Hold function of alarm, Heater break alarm
(refer to alarm type and code)
·Setting range : Process alarm ...... 0 ~ 100 % of instrument range
Deviation alarm ...... -100 ~ 100 % of instrument range
·Alarm hysteresis : 0.0 ~ 100.0 % of instrument range
HBA
·Current measurement range : 1 - 50 A a.c. (resolution: 0.5 A, ±5 % ±1 digit of FS)
·Alarm output : Selectable in alarm output ·Dead band: 0 ~ 100 % of max. range
·HBA is available during ON/OFF control or time proportional output
(but not during current output or cooling output)
·Break detection is not possible below 0.2 sec. during output on.
▍
Power supply
Power voltage
100 - 240 V a.c. (Voltage fluctuation rate : ±10 %)
Frequency
50/60 ㎐
Power consumption Max. 6.0 W, max. 10 VA
Insulation
resistance
Between primary terminal and secondary terminal : min. 500 V d.c., 20 ㏁
Between primary terminal and ground : min. 500 V d.c., 20 ㏁
Between ground and secondary terminal : min. 500 V d.c., 20 ㏁
Dielectric strength
Between primary terminal and secondary terminal : 2,300 V a.c. 50/60 Hz for 1 min.
Between primary terminal and ground : 2,300 V a.c. 50/60 Hz for 1 min.
Between F•G and secondary terminal : 1,500 V a.c. 50/60 Hz for 1 min.
Sensor power supply 24 V d.c. 20 mA (but, it is not available in retransmission output)
▍
Interface
Standard
EIA RS485
Max number of
connections
31 addresses can be set from 1 to 99
Communication
method
2-wire half-duplex
Synchronization Asynchronous
Communication
sequence
None
Communication
distance
Within 1.2 km
Communication speed 600, 1200, 2400, 4800, 9600 BPS (Speed is changeable by parameter setting)
START BIT
1 BIT
DATA BIT
7 or 8 BIT
PARITY BIT
None, even numbers, odd numbers
STOP BIT
1 or 2 BIT
PROTOCOL
PC LINK WITHOUT SUM(0), PC LINK WITH SUM(1)
Response time
Reception handling time + (Response time × 10 ms)
4-Ø4
제3설정(SV3)표시
제2설정(SV2)표시
제어출력(OUT)표시
설정치(SV)표시
측정치(PV)표시
경보2(AL2)표시
경보1(AL1)표시
오토튜닝(AT)표시
설정치 증가 키
설정치 감소 키
설정행 이동 키
모드진입/설정 키
표시부
Cable 26P
제어부
4-Ø4
4-Ø4
제3설정(SV3)표시
제2설정(SV2)표시
제어출력(OUT)표시
설정치(SV)표시
측정치(PV)표시
경보2(AL2)표시
경보1(AL1)표시
오토튜닝(AT)표시
설정치 증가 키
설정치 감소 키
설정행 이동 키
모드진입/설정 키
표시부
Cable 26P
제어부
4-Ø4
Power
100 - 240 VAC
F.G
B- B+ A
RTD
T.C
RTX+
SG
RTX-
DI2
(SV2)
OUT1
OUT1
SSR/SCR/RET
SSR/SCR/RET
CT
DI1(SV1)
OUT2
OUT2/AL2
AL1
▍Dimension
■ Display
■ Connection diagram
■ Control
■ Part name
※Cable length basically 300 ㎜
Display
Cable 26P
Control
Ø
Ø
The 3rd setting display
The 2nd setting display
Control output display
Set Value display
Process Value display
Alarm 2 display
Alarm 1 display
Auto-tuning display
Increase setting button
Decrease setting button
Shift setting button
mode/setting button