Hanyoung PX2 series Instruction Manual Download Page 1

PX series

INSTRUCTION MANUAL

Thank you for the purchase of HANYOUNG product.
Please read this manual carefully.

Process Controller

هرﮐ

 

ﮓﻧﺎﯾﻧﺎھ

 

تﻻوﺻﺣﻣ

 

یرﺎﺻﺣﻧا

 

هدﻧﯾﺎﻣﻧ

 

ناوﯾﺳ

 

تﮐرﺷ

021-33989001

www.sivancarno.com

021-33989002

Summary of Contents for PX2 series

Page 1: ... INSTRUCTION MANUAL Thank you for the purchase of HANYOUNG product Please read this manual carefully Process Controller ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 2: ...UREMENT RANGE 13 OUTPUT GROUP SETTING 14 SET VALUE GROUP SETTING 15 PROGRAM GROUP SETTING 16 AUTO TUNING 17 P I D GROUP 18 ALARM GROUP SETTING 19 ALARM TYPE AND CODE 20 RETRANSMISSION GROUP 21 COMMUNICATION 22 HEATER BREAK ALARM GROUP 23 REMOTE INPUT GROUP P 3 P 5 P 5 P 6 P 10 P 11 P 12 P 13 P 15 P 16 P 17 P 18 P 19 P 20 P 21 P 22 P 23 P 24 P 25 P 26 P 26 P 27 P 27 ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧ...

Page 3: ...k function Heating Cooling Zone PID Group PID Power supply for sensor Output Limits Interface RS485 422 3 Set points Heater break alarms HBA1 HBA2 IP65 Front facia High Accuracy 0 1 class 250 ms Features PX Series ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 4: ... malfunction 5 Caution on maintenance Turn OFF the power before mounting or removing the instrument To ensure continuous and safe operation of the instrument periodical maintenance is recommended Some parts are limited in life The warranty period is 1 year only if using in the correct way CAUTION 1 Caution on handling Do not install the instrument under any of the following conditions The ambient ...

Page 5: ...nd the instrument power supply should be connected using the same power suppy when a heater break alarm Time for preparation of contact output is required at power ON When the output signal is used for an extenal interlock circuit connect a delay relay 4 For load circuit connection Use an extra relay when the frequency of operation is rather high SSR output type is recommended Electromagnetic swit...

Page 6: ...al output Retransmission Communication RS485 422 Power supply for sensor 22 types of alarm Sampling cycle 250 ms 0 1 FS high accuracy ORDERING INFORMATION INSTRUCTION 2 3 PX2 Process Controller 48 96 mm Universal Heating Cooling 0 1 Description Suffix code Model PX3 Process Controller 96 48 mm Universal Heating Cooling 0 1 Description Suffix code Model PX9 Process Controller 96 96 mm Universal Hea...

Page 7: ... DIN 1 5 15 35 2 0 15 50 OFF Up Down scale selectable Thermocouple burn out Up Down scale R T D burn out Up scale TC R T D burn out detection current Approx 50 0 1 of F S SPECIFICATION 4 100 240 V 24 V 50 60 Hz 10 10 Max 6 0 W 10 VA or below 27 V 20 mA but it is not available when using retransmission output 20 min at 500 V DC Between primary terminal and secondary terminal Between primary termina...

Page 8: ...uto tuning ON OFF hysteresis 0 100 Time resolution 0 1 or 10 ms ON voltage 12 V DC min Resistance load 600 min 30 mA limit when short OFF voltage 0 1 V DC max Output action Proportional action Proportion cycle time 1 1000 sec Output limit Higher OH or lower limit OL selectable within 0 0 100 0 range It is also available in AT and MAN Time resolution 0 1 or 10ms whichever is larger Output current r...

Page 9: ...0 A AC Resolution 0 5 A 5 of F S 1 Digit Alarm output AL1 2 output It is available to use in ON OFF or proportional action not available in current or cooling output Minimum detection time 0 2 sec Dead Band 0 100 SAFETY AND EMC STANDARDS Safety and EMC Standards Safety standards IEC1010 1 1990 and EN61010 1 1992 CSA1010 CAT IEC1010 1 and UL508 EMC Standards EN55011 Class A Group 1 for emission EMS...

Page 10: ...ENSIONS PANEL CUTOUT 5 Unit mm PX2 48 96 mm PX7 72 72 mm PX3 96 48 mm PX9 96 96 mm CURRENT TRANSFORMER Model CTL 6 S ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 11: ...ting alarm outputs AL1 AL2 Note Heater break alarm is used by setting alarm outputs AL1 AL2 AL3 Optional Optional 1 Optional 2 Optional 3 PX9 96 96 mm PX2 48 96 mm PX3 96 48 mm PX7 72 72 mm ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 12: ...e operation mode to the setting mode to select parameters and to register set value Press this key for 3 sec to display setting mode set value and process value Used to select digit for changing Used to decrease set values and to select setting mode Used to increase set values and to select setting mode Name of respective parts Process value PV Set value SV Remote indicator Set value display indic...

Page 13: ...ting of 3 group Manual reset P I D setting of 3 group for cooling Heating Cooling hysteresis Zone section Detection current of HBA 1 Detection current of HBA 2 Alarm 1 hysteresis Alarm 2 hysteresis Measuring current of Alarm 1 Measuring current of Alarm 2 Select number of setting mode Set SV 1 Set SV 2 Set SV 3 Auto tuning type Auto tuning start type Group Program Group Set value Group Autotuning ...

Page 14: ...ss Response time Group Alarm Group Retransmission Group Communication Group Remote Group Output Group Input Cycle time of cooling side in heating cooling type Hysteresis Output volume when input disconnection output 1 Output volume when input disconnection output 2 Maximum value of output Minimum value of output Setting and Display level select This controller has 3 different levels of setting the...

Page 15: ...press to indicate an auto output value 3 Sec Auto output value display Manual output setting and display or Heating Cooling Universal 3 Sec 3 Sec After checking wiring power ON Set the whole setting after select 3 as below After finishing select 1 to prevent an error in setting Make display range to be same as level setting range so that not to be shown other display group which is not needed Cont...

Page 16: ... DI 2 are ON it is same Initial value is OFF None DI 1 DI 2 DI 1 DI 1 DI 2 DI 1 DI 2 DI 1 DI 2 OFF ON OFF ON ON OFF OFF OFF OFF ON ON OFF Chart1 Local Program or Remote is selected in the control group mode using or key When selecting LOCAL mode control zone selection and fuzzy function selection are available Control zone selection is not available when selecting program mode or remote mode Fuzzy...

Page 17: ... set 1 0 0 set 2 0 00 set 3 0 000 Maximum and Minimum on scale It is the same function as Maximum and Minimum range setting when R T D or thermocouple input This mode is indicated when voltage input 30 32 33 PV filter When PV value becomes unstable due to effects of noise the filter helps suppress the unstable status Range OFF or 1 120 sec Initial value OFF PV bias Use this function to adjust PV v...

Page 18: ...rement range unit High limit Low limit Decimal point Maximum on scale on voltage input Minimum on scale on voltage input PV filter PV bias Burn out Input type and mode selection Refer to input signal and range Refer to input signal and range Notice FR H FR L Thermocouple or R T D decimal point of instrument DC Voltage 0 3 1999 9999 Notice SL H SL L Deimal point according to DP P OFF 1 120 sec EUS ...

Page 19: ...en Type of control output Universal type This process controller is divided into 2 types UNIVERSAL TYPE AND HEATING COOLING TYPE Output is selectable from Relay SSR and Current 4 20mA DC Output type range output code is for universal type and for Heating Cooling type Sometimes retransmission output and alarm output are not available according to control output EX When you choose output code OT 2 i...

Page 20: ...lay Relay Relay SSR SSR SSR Current Current Current Retransmission Retransmission Retransmission Model 4 5 6 7 8 9 10 11 12 Cooling OUT2 Heating OUT1 Output code O T SSR Current Relay SSR Current Retransmission Relay Initial value Condition Description Name Signal Set value group Select number of set value Set SV 1 Set SV 2 Set SV 3 Set value setting 1 3 EU 0 0 100 0 EU 0 0 100 0 EU 0 0 100 0 REM ...

Page 21: ...ntrol the controller becomes a programmable ramp soak controller with 1 pattern of 10 step After setting time and set value this controller controls automatically A pattern is a series of steps Each step consists of a SV and time setting An Increasing or decreasing SV is set for time period and each time setting is in hours minutes or minutes seconds After wiring check and power ON PV and SV will ...

Page 22: ...the set value Use this type where overshoot is to be suppressed Auto tuning The Auto tuning function automatically measures computes and set the optimum P I D and ARW contants The Auto tuning function can be activated at any time during the process after power ON while temperature is rising or when control has stabilized Auto tuning is not operated when selecting OFF in selection mode of auto tuni...

Page 23: ...3 Set point of Zone 2 2 RP Set point of Zone 1 1 RP Maximum Range Eu 100 Minimum Eu 0 Zone 2 Zone 1 When checking P I D values or setting SV in manual mode this can be done in P I D Group Press key to get Anti Reset Wind value by auto or manual and then press once more to be indicated P I D mode which is selectable 3 types of P I D group 0 3 Example 0 is no P I D mode and after Auto tuning 1 using...

Page 24: ...and and value of each alarm Refer to the next page for the 19 different types of alarm functions In Heating Cooling type of PX7 is not indicated when selecting 10 11 12 In PX7 is not indicated because of no third alarm output In Heating Cooling type of PX3 PX2 PX9 is not indicated when selecting 10 11 12 18 Reference Display lamp will be OFF when output ON in inverted type Without hold function Lo...

Page 25: ... function High deviation with hold function Low deviation with hold function High deviation with hold function inverted Low deviation with hold function inverted High Low deviation with hold function High Low band with hold function High absolute value with hold function inverted Low absolute value with hold function inverted Heater break alarm 1 HBA 1 Heater break alarm 2 HBA 2 Function ALARM TYP...

Page 26: ...isson will not be indicated PV COMMUNICATION Communication group RS485 RS422 Protocol Communication rate B P S Parity check Stop bit Data length Address Response time Set communication mode PC LINK Set value 0 PC LINK SUM Set value 1 600 SV 0 1200 SV 1 2400 SV 2 4800 SV 3 9600 SV 4 NONE SV 0 EVEN SV 1 ODD SV 2 1 bit SV 1 2 bit SV 2 7 bit SV 7 8 bit SV 8 Except PC LINK 8 1 99 maximum 31 devices 0 1...

Page 27: ...by remote set In remote condition SV is changeable by front keys but the controller is controlled by external set value Do not change set value by remote in auto tuning Set remote mode 1 000 5 000 V but R INH R INL Thermocouple FR H FR L DC voltage SL H SL L Decimal point is set by DP P OFF 1 120 EUS 100 0 100 0 HEATER BREAK ALARM GROUP Heater break alarm group consist of output dead band and curr...

Page 28: ... ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 29: ... ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...

Page 30: ...MA0201E050117 ﮐره ھﺎﻧﯾﺎﻧﮓ ﻣﺣﺻوﻻت اﻧﺣﺻﺎری ﻧﻣﺎﯾﻧده ﺳﯾوان ﺷرﮐت 021 33989001 www sivancarno com 021 33989002 ...