background image

3

MK0101KE180920

Danger

Warning

Caution

   Analog Temperature Controller

  

HY-4500/4700/5000

 

       Thank you for purchasing HANYOUNG product.
       Please check whether the product is the exactly same as you ordered. 
       Before using the product, please read this instruction manual carefully.
       Please keep this manual where you can view at any time

 INSTRUCTION MANUAL

1381-3, Juan-Dong, Nam-Gu Incheon, Korea.  
TEL:(82-32)876-4697 FAX:(82-32)876-4696 http://www.hynux.net

HANYOUNGNUX CO.,LTD

HEAD OFFICE

Safety information

Before using the product, please read the safety information thoroughly and use it properly.Alerts 

declared in the manual are classified to Danger, Warning and Caution by their criticality

There is a danger of occurring electric shock in the input/output terminals so please never let 

your body or conductive substance is touched.

•If there is a concern about a serious accident caused by a malfunction or abnormality of this 

   product, please install an external protection circuit and devise a scheme for preventing an accident.

•This product does not contain an electric switch or fuse, so the user needs to install a 

   separate electric switch or fuse externally. (Fuse rating: 250 V 0.5 A)

•To prevent defection or malfunction of this product, apply a proper power voltage in 

   accordance with the rating.

•To prevent electric shock or malfunction of product, do not supply the power until the wiring is completed.

•Since this product is not designed with explosion-protective structure, do not use it any place 

   with flammable or explosive gas.

•Do not decompose, modify, revise or repair this product. This may be a cause of malfunction, 

   electric shock or fire.

•Reassemble this product while the power is OFF. Otherwise, it may be a cause of malfunction or electric shock.

•If you use the product with methods other than specified by the manufacturer, there may be 

   bodily injuries or property damages.

•There is a possibility of occurring electric shock so please use this product after installing it 

   onto a panel while it is operating.

•The contents of this manual may be changed without prior notification.

•Before using the product you purchased, make sure that it is exactly what you ordered.

•Make sure that there is no damage or abnormality of the product during the delivery.

•Use this product within the range of the operating ambient temperature, 0 ~ 50 ℃ (When it is 

   closely installed Max 40 ℃) and ambient humidity, 35 ~ 85 % R.H (No condensation).

•Do not use this product at any place with occurring corrosive 

   (especially noxious gas or ammonia) or flammable gas.

•Do not use this product at any place with direct vibration or impact.

•Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron 

   contents.(Use at Pollution level 1 or 2)

•Do not polish this product with substances such as alcohol or benzene. (Use neutral detergent.)

•Do not use this product at any place with a large inductive difficulty or occurring static 

   electricity or magnetic noise.

•Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation.

•Install this product at place under 2,000m in altitude.

•When the product gets wet, the inspection is essential because there is danger of an electric leakage or fire.

•In case of inputting thermocouple, use a compensating cable. 

   (If using a normal wire, there is a possibility of occurring temperature error.)

•For R.T.D input, use a cable which is a lead wire has small resistance and resistances of three wires 

   shall be the same. (If the three wires have different resistances then there will be a temperature error.)

•To avoid an effect of inductive noise to input signal cables, use the product after separating 

   the input signal cables from power, output and load cables.

•Separate an input signal cable from an output signal cable. If separating is not possible, 

   please use the input signal cable after shielding it.

•Use non-earth sensor with thermocouple. (In case of using earth sensor, there is a possibility 

   of occurring malfunction caused by a short circuit.)

•If there is excessive noise from the power supply, using insulating transformer and noise filter is 

   recommended. The noise filter must be attached to a panel which is already connected to a ground 

   and the wire between the filter output side and power supply terminal must be short as possible.

•If twisting the power cables closely together then it is effective against noise.

•If the alarm functions are not properly set then it will not be output when the product is 

   malfunctioning. Therefore, make sure its movements are properly working before the operation.

•Turn the power OFF when replacing a sensor.

•Use an auxiliary relay in case of high frequent operation such as proportional operation or etc. 

   its life span will be shorter if connecting a load without permissible rating of output relay. In this 

   case, using SSR output type is recommended.

  ·Life Span of Contact Point Output : 

      Mechanical Life Span: above 10 million times (with no load)

      Electrical Life Span: 100 thousand times (250 V a.c 3 A: with the rated load)

•Do not connect anything to the unused terminals.

•After checking the polarity of terminal, connect wires at the correct position.

•When this product is connected onto a panel, use a circuit breaker or switch approved with IEC60947-1 or IEC60947-3.

•Install a circuit breaker or switch at near place for convenient use.

•Write down on a label that if the circuit breaker or switch is operating then the power will be 

   disconnected since the circuit breaker or switch is installed.

DANGER

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

WARNING

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury

Suffix code

•For the continuous and safe use of this product, the periodical maintenance is recommended.

•Some parts of this product have limited life span, and others are changed by their usage.

•The warranty period for this product including parts is one year if this product is properly used.

•When the power is on, the preparation period of contact output is required. In case of using 

   signals of external interlock circuit or etc., use it with a delay relay.

•In case of replacing this unit with a spare unit, make sure its compatibility because its operation 

   can be different by different parameter settings even though the model name is the same.

•Before using a temperature controller, there could be a temperature difference between PV of 

   the temperature controller and the actual temperature so please operate the temperature 

   controller after compensating the temperature difference appropriately.

Range and Input code chart

Dimension and Panel cutout

█ HY-5000

[Unit : mm]

Model

Code

Description

HY-

     

Analog indication temperature controller

Dimension

4500S

96(W) × 96(H)

4700S

96(W) × 96(H) (Auxiliary output : L.M)

5000S

72(W) × 72(H)

Control type

F

ON/OFF control (2 position control)

P

Proportional control

Input

K

K thermocouple

J

J thermocouple

R

R thermocouple

P

RTD Pt100 Ω(IEC)

V

1 - 5 V d.c

C

4 - 20 mA d.c

Control output

M

Relay

C

Current output (4 - 20 mA d.c)

S

S.S.R (12 V d.c Voltage pulse output)

Sub output (L.M)
(Apply only with the model 
HY-4700)

N

None

O

High action

P

Low action 

W

High·Low action 

Control operation

R

Reverse action (Heating control)

D

Direct action (Cooling control)

Range code

Select the standard range code

              Model
Code No

HY-4500S, HY-4700S

HY-5000

Input

Range (℃)

Input

Range (℃)

1

Pt100 Ω

-50 ~ 50

Pt100 Ω

-50 ~ 50

3

Pt100 Ω

-50 ~ 100

Pt100 Ω

0 ~ 100

5

Pt100 Ω

0 ~ 100

K, Pt100 Ω

0 ~ 200

6

-

-

K, Pt100 Ω

0 ~ 300

7

K, Pt100 Ω

0 ~ 200

K, Pt100 Ω

0 ~ 400

8

K, Pt100 Ω

0 ~ 300

K

0 ~ 600

9

K, J, Pt100 Ω

0 ~ 400

K

0 ~ 800

10

K

0 ~ 600

K

0 ~ 1200

11

K

0 ~ 800

-

-

13

K

0 ~ 1200

-

-

14

R

0 ~ 1600

-

-

INDONESIA

FACTORY

JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
LIPPO CIKARANG CICAU, CIKARANG PUSAT BEKASI 17550 INDONESIA
TEL : 62-21-8911-8120~4  FAX : 62-21-8911-8126 

PT. HANYOUNG ELECTRONIC INDONESIA

Reviews: