DAD 141.1 Technical Manual, Rev. 2.5 – April 2015
Page 18 of 54
7.7. Menu 5
– Analog Output
Remark: Activate a new setup with 1x Power OFF & ON !
5
Analog output setup
(Menu 5.1 to 5.5)
5.1
Weight value for minimum analog output
(command AL)
- Set the weight value which corresponds to minimum output
Examples
for scale 0 … 3 000kg
Minimum 0kg or with 600kg preload
-
output mode 4 … 20mA:
0kg = 4mA - setting 00000
600kg = 4mA - setting 00600
-
output mode 0 … 20mA:
0kg = 0mA - setting 00000
600kg = 0mA - setting 00600
5.2
Weight value for maximum analog output
(command AH)
- Set the weight value which corresponds to maximum output
Examples
for scale 0 … 3 000kg
Maximum 3 000kg
-
output mode 4 … 20mA:
3 000kg = 20mA - setting 03000
-
output mode 0 … 20mA:
3 000kg = 20mA - setting 03000
5.3
Analog output base
(command AA)
gros - analogue output follows G
ross
value
net - analogue output follows N
et
value
PEA - analogue output follows P
eak
value (Maximum)
AUEr - analogue output follows A
verage
value
HoLd - analogue output follows H
old
value
PP - analogue output follows
Peak - Peak
value
UALL - analogue output follows
Valley
value (Minimum)
dISP - analogue output follows
Display
value
oFF - analogue output is switched
OFF
5.4
Analog output mode
(command AM)
4_20
4 to 20mA
0_20
0 to 20mA
0 _ 5
0 to +5V
0 _ 10
0 to +10V
- 5 _ 5
-5 to +5V
- 10 _ 10
-10 to +10V
5.5
Setup of test signal current or voltage analog output
The test signal, independent of the measuring signal, is based
on the choosen mode in menu
5.4
. The setup uses 6 digits,
e.g. 004.000 for 4mA (decimal point position is fixed). For each
mode you can use the output range plus -/+ 0.1 ! Setup of a
negative value via left figure/“
-
“ sign (left status LED).