System Application
7.1
Principle& Application of economizer
RC2-D series compressor is equipped with economizer stop valve as standard. The stop valve can be
rotated and locked with internal and external thread of flange, and can be connected in any direction,
which is convenient for use.
The economizer’s pressure is very close to the intermediate pressure of Hanbell compressor, this
economizer port design can realize no compression backflow loss, so as to ensure that the
compressor can maintain the best operation state in the whole load stage.
With these characteristics,
if the screw compressor can be designed to add a system of subcooling circuit or a flash drum for
two-stage expansion to inject gas into the economizer port, it is possible to improve the efficiency.
Especially under the condition of high compression ratio, the power consumption of the compressor
increases very little, which can not only achieves a better energy efficiency ratio, but also improves
the refrigeration capacity, efficiency and reliability of the system.
Please get efficiency of the economizer through hanbell selection program.
7.1.1
Sub-cooled Economizer System
The subcooled economizer system uses a heat exchanger (subcooler) to subcool the liquid refrigerant.
A part of the refrigerant from the condenser is injected into the subcooler, and the throttled
refrigerant will evaporate and absorb heat in the subcooler, so as to achieve the subcooling effect.
The superheated steam enters the compressor through the economizer and mixes with the partially
compressed gas from the evaporator. Because the supercooled liquid is under the condensation
pressure, there is no special requirement for the connecting pipeline between the supercooled liquid
and the evaporator, only the heat insulation is needed. This system is suitable for general application.
图7-1 经济器系统示意图(过冷式)
Summary of Contents for RC2-D
Page 27: ...RC2 D Technical Manual 2 RC2 200 470 D S P terminal box 3 RC2 510 930 D S P terminal box ...
Page 45: ...RC2 D Technical Manual 47 RC2 180D S Drawing ...
Page 46: ...RC2 D Technical Manual 48 RC2 200 620D S Horizontal suction port Drawing ...
Page 48: ...RC2 D Technical Manual 50 RC2 620 930D S Vertical suction port Drawing ...
Page 49: ...RC2 D Technical Manual 51 10 2 RC2 100 930D P Drawing RC2 100 140D P Drawing ...
Page 50: ...RC2 D Technical Manual 52 RC2 180D P Drawing ...
Page 51: ...RC2 D Technical Manual 53 RC2 200 620D P Drawing ...
Page 53: ...RC2 D Technical Manual 55 RC2 620 930D P Drawing ...