RC2-D Technical Manual
Maximum operating current definition (MCC):
maximum load current of compressor motor running.
Motor: Mainly used for R22, R404A, and R507 refrigerant
Frequency: 50Hz; Voltage: 380V
Frequency: 50Hz; Voltage: 380V
Model
MCC(A)
LRA(A)
Model
MCC(A)
LRA(A)
RC2-100D-S(P)
55
245
RC2-410D-S(P)
208
740
RC2-140D-S(P)
72
330
RC2-470D-S(P)
245
840
RC2-180D-S(P)
91
490
RC2-510D-S(P)
250
840
RC2-200D-S(P)
99
490
RC2-550D-S(P)
280
925
RC2-230D-S(P)
119
510
RC2-580D-S(P)
300
925
RC2-260D-S(P)
129
510
RC2-620D-S(P)
317
1295
RC2-300D-S(P)
148
645
RC2-710D-S(P)
360
1410
RC2-310D-S(P)
157
645
RC2-790D-S(P)
382
1510
RC2-340D-S(P)
174
730
RC2-830D-S(P)
429
1640
RC2-370D-S(P)
188
780
RC2-930D-S(P)
491
2090
Table 4-1 RC2-D series compressor MCC&LRA
Note:
MCC in table 4-1 above will vary depending on voltage and frequency.
4.4
Wiring diagram of terminal cover plate
4.5
Grounding
There is a ground wire connector in the terminal box. Please make sure it is connected with the ground
wire.
Note:
a.
The setting of leakage protector should be more than 50mA;
In humid area, the setting should be
changed to 25mA
Summary of Contents for RC2-D
Page 27: ...RC2 D Technical Manual 2 RC2 200 470 D S P terminal box 3 RC2 510 930 D S P terminal box ...
Page 45: ...RC2 D Technical Manual 47 RC2 180D S Drawing ...
Page 46: ...RC2 D Technical Manual 48 RC2 200 620D S Horizontal suction port Drawing ...
Page 48: ...RC2 D Technical Manual 50 RC2 620 930D S Vertical suction port Drawing ...
Page 49: ...RC2 D Technical Manual 51 10 2 RC2 100 930D P Drawing RC2 100 140D P Drawing ...
Page 50: ...RC2 D Technical Manual 52 RC2 180D P Drawing ...
Page 51: ...RC2 D Technical Manual 53 RC2 200 620D P Drawing ...
Page 53: ...RC2 D Technical Manual 55 RC2 620 930D P Drawing ...