User Manual RCx-B-xxxAx-8.09
Page 4 of 18
www.hanbayinc.com | 1 800 315 4461
Rev.2021.8 [email protected]
Wiring for Non-Explosion Proof actuators
The actuator comes standard with a pre-
installed cable gland and a 10’ cable. Cut the cable to the length
required, then connect according to the following wire color schematic:
Wire color schematic for cable
Power Supply and Current Draw
The
RCx-AC-B-xxxAx
actuator
may be connected to voltages within 110-240 VAC.
The current draw will range from minimum 10 mA to maximum 1.5 A while the actuator is active. When not
moving, the actuator draws approx. 5 mA.
AC power is connected to the
RED
&
BLACK
wires with
crimp connectors (WM18225-DN & WM18230-ND 18-22
AWG).
Ground is connected on the panhead ground screw, circled
in yellow.
Colour
Function
Red (1)
Live 110-240 VAC (16 AWG)
Black (2)
Neutral 110-240 VAC (16 AWG)
Blue (3)
Ground (16 AWG)
Green (4)
Not connected
Grey (5)
Feedback* signal (20 AWG)
Yellow (6)
Isolated
**
input signal gnd. (20 AWG)
Blue (7)
Isolated
**
input s
ignal 4…20 mA (20 AWG)
* “feedback” available in RCx-AC-xxxA
F
version only
** “isolated” available in RCx-AC-xxxA
I
and xxxA
F
versions only
Remove sensing resistor R66 to convert
from 4-20 mA to 1-5 V control signal
Note:
if R66 is removed, we recommend
placing a 10K resistor between signal and
signal GND or simply using shielded cable
(for noise reduction).