User Manual MCx-xxxAS-1.05
Page 2 of 18
www.hanbayinc.com | 1 800 315 4461
Rev.2021.8 [email protected]
Terminal
1 2 3 4 5 6
Remove R66 to
convert from 4-20 mA
to 1-5 V input signal
INSTALLATION
Mounting
In most cases, the actuator must be mounted
and supported as shown in the image to the
right. The mounting bracket is not supplied by
Hanbay.
Exceptionally, the actuator may be suspended
on the tubing itself but ONLY if the application is
vibration free a
nd the tubing is minimum ¼” dia.
stainless.
Wiring
The actuator comes standard with a Turck 6 position connector
and a 20’ cable with plug. Cut the cable to
the length required and then connect according to the following wire color schematic. Pins indicate the
connection of the cables to the terminal block on the PCB board within the actuator. Unless specified by
the customer, these are pre-wired at the factory.
Wire color schematic for
“Turck 6” cable:
If you have chosen to exclude the Turck cable from your order, connect the wires to the corresponding pins
on the terminal block as indicated in the schematic:
Pin
Color
DC power supply only
6
White
+24 VDC
5
Black
Power Gnd
4
Pink
TD(A)
3
Grey
TD(B)
2
Brown
Isolated Input Signal Gnd
1
Blue
Isolated Input + Signal (4-20 mA)
Mounting
Bracket
Cable Entry