background image

Melbury HE, C 530 - 3000 

11 

We reserve the right to make changes to dimensions and construction 

edition 12.2020 

Hamworthy Heating Limited – Dorset BH17 ONF 

 

 

 

 

4.5.  Dimensions of custom-made models 

 

The following custom-made models are available on request. They are however subject to different delivery 

times! 

 

 

4.5.1.  Vertical flue connection Melbury HE  

 

 

Melbury HE 

 

 

530 

580 

630 

700 

800 

895 

1150  1300  1650 

1900  2500  3000 

Flue outside 

diameter 

mm 

200 

250 

250 

250 

250 

300 

350 

350 

350 

400 

450 

500 

Flue height 

f

1

 

mm 

60 

100 

100 

100 

100 

100 

80 

80 

80 

80 

80 

80 

Flue position 

mm 

1702 

1812 

1812 

2025 

2025 

2106 

2459 

2459 

2819 

3004 

3260 

3521 

Overall length 

L

1

 

mm 

2025 

2140 

2140 

2360 

2360 

2465 

2859 

2859 

3274 

3484 

3766 

4051 

Overall height 

H

1

 

mm 

1370 

1470 

1470 

1555 

1555 

1645 

1730 

1730 

1805 

1870 

1990 

2080 

16/10/07 RR 

 

The other dimensions are identical to those of the standard range. 

 

 

4.5.2.  Different operating pressures 

 

Melbury HE and C boilers can be provided for the operating pressures of 4, 8 and 10 bar-g. Their dimensions 

and performances are identical to those of the standard range of 6 bar-g, but their weights are different: 

Empty weights 

Melbury HE 

 

 

530 

580 

630 

700 

800 

895 

1150 

1300 

1650 

1900 

2500 

3000 

4 bar 

kg 

1127 

1439 

1439 

1802 

1802 

1959 

2302 

2302 

2753 

3194 

3937 

4440 

8 bar 

kg 

1190 

1606 

1606 

1979 

1979 

2159 

2715 

2715 

3286 

3761 

4601 

5221 

10 bar 

kg 

1277 

1608 

1608 

2227 

2227 

2436 

2746 

2746 

3362 

4053 

4980 

5706 

16/10/07 RR 

 

16/10/07 RR 

 

Empty weights 

Melbury C 

 

 

530 

580 

630 

700 

800 

895 

1150 

1300 

1650 

1900 

2500 

3000 

4 bar 

kg 

1447 

1749 

1749 

2152 

2152 

2379 

2792 

2792 

3313 

3934 

4857 

5510 

8 bar 

kg 

1510 

1916 

1916 

2329 

2329 

2579 

3205 

3205 

3846 

4501 

5521 

6291 

10 bar 

kg 

1597 

1918 

1918 

2577 

2577 

2856 

3236 

3236 

3922 

4793 

5900 

6776 

16/10/07 RR 

 

16/10/07 RR 

 

 

4.5.3.  Melbury C sanitary version 

 

The recuperators of the Melbury C 530 to 1650 can be provided as sanitary version with water collectors and - 

connections made of stainless steel. Their dimensions and performances are identical to those of the standard 

range, apart from the dimensions of the water connections (see table in chapter 4.4.2). 

Summary of Contents for Melbury C 1150

Page 1: ...Manual Melbury GB doc edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF Installation and operating instructions Melbury HE C 530 3000...

Page 2: ......

Page 3: ...al equipment 20 5 4 Heating regulators 20 5 5 Cable sets 20 6 Installation guide 21 6 1 Boiler room and boiler room ventilation 21 6 2 Planning dimensions 21 6 3 Hydraulic connection 23 6 4 Electrical...

Page 4: ...parts of the body or without wearing shoes When the unit is not to be used for a longer period the main power switch on the electrical control panel must be switched off and the manual valve on the un...

Page 5: ...e control and safety mechanisms required by local regulations in force The line must be free from all impurities take particular care that foreign matter does not enter the line during installation Oi...

Page 6: ...kept down to a minimum and thermal radiation can be further reduced A revolving door gives easy access to parts of the boiler that are in contact with combustion gases This allows cleaning of combusti...

Page 7: ...pe of supply Boiler body with recuperator in Melbury HE C version flue gas collector and flue gas tube Gas tight boiler door with insulation and burner connection and flue gas fan connection if ordere...

Page 8: ...es must be thoroughly cleaned The purpose of this initial cleaning is to eliminate germs and residue that can cause deposits to form In new installations in particular residue from grease oxidized met...

Page 9: ...uipment materials and quickly disappears Without refreshing the oxygen through significant contributions of water the unit might not experience any damage whatsoever However it is important to follow...

Page 10: ...ations of the boiler must be as low as possible to ensure the highest service life The first heating must allow the evacuation of moisture from concrete doors it is necessary to avoid any heat shock a...

Page 11: ...0 150 150 200 200 200 238 238 274 292 318 344 Distance supply return j mm 950 950 950 1150 1150 1150 1493 1493 1727 1844 2000 2168 Discharge height k mm DN 80 1 100 1 100 1 115 1 115 1 125 1 110 1 110...

Page 12: ...25 1 1 1 0 1 1 1 0 1 1 07 1 1 03 1 1 00 1 1 1 0 1 Distance recuperator water studs recup backside m mm 285 285 285 305 305 335 385 385 455 flow return recuperator n DN 65 80 80 80 80 100 100 100 125...

Page 13: ...for the operating pressures of 4 8 and 10 bar g Their dimensions and performances are identical to those of the standard range of 6 bar g but their weights are different Empty weights Melbury HE 530 5...

Page 14: ...2674 2854 3096 3356 b mm 1000 1060 1130 1210 1300 1375 1445 1570 1645 c1 mm 661 712 740 790 863 875 905 965 1027 c2 mm 480 552 565 605 650 690 779 840 845 d mm 900 900 1000 1070 1210 1290 1360 1480 1...

Page 15: ...60 80 min qF 94 8 94 9 94 9 94 9 94 9 95 0 95 0 95 0 95 0 95 0 95 1 95 0 E C fficiency DIN4702 8 60 75 C N 94 4 94 6 94 5 94 8 94 6 94 8 94 8 94 7 94 6 94 7 94 8 94 7 Mass flows Fuel oil flow max 1 kg...

Page 16: ...low NG type E max 1 2 nm 3 h 58 7 63 4 69 3 76 2 87 9 97 0 125 2 142 7 182 1 208 6 273 4 331 1 min 1 2 10 0 12 9 12 9 18 1 18 1 27 4 33 5 33 5 38 5 47 8 75 9 74 9 Exhaust gas mass flow max wet kg s 0...

Page 17: ...5 16 0 17 5 21 5 22 5 29 5 34 5 37 0 45 0 55 0 73 0 84 0 Values at 3zugskessel V 01 07 lamda 1 2 CO2 12 7 OG T air 20 C rel humidity 60 p baro 100kPa 1 Boiler at 60 80 C 2 Boiler at 50 70 C Technical...

Page 18: ...ght to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 4 7 2 Water resistance of recuperators for Melbury C Pressure resistance in relation to wat...

Page 19: ...an average boiler water temperature of tm 70 C Since the minimum power of the boiler is limited by the minimum allowable flue gas temperature the modulation range increases when the average boiler tem...

Page 20: ...temperatures TR at boiler nominal loads as well as 50 load for 180 C nominal inlet temperature Values at CO2 12 7 t water 5 K Rel humidity 60 p baro 100 kPa Condensate amount per kg of fuel oil and f...

Page 21: ...at CO2 10 t water 5 K Rel humidity 60 p baro 100 kPa Condensate amount per nm3 of gas and flue gas temperatures for different flue gas inlet temperatures and recuperator return temperatures TR at boi...

Page 22: ...tic hot water etc The steel sheet housing is ready to be mounted on top of the boiler cover or on the carrier located on the side cover The electrical diagram is attached to the control panel 5 2 Basi...

Page 23: ...are found in spray cans thinners cleaning agents degreasing agents and solvents among others In addition halogen emissions are strongly suspected in the vicinity of dry cleaners hair dressing salons s...

Page 24: ...4 4 4 4 6 6 6 U girder width S1 mm 50 50 50 55 55 55 55 55 55 55 55 55 Melbury C 530 580 630 700 800 895 1150 1300 1650 1900 2500 3000 Distance wall boiler body front D mm 1600 1700 1700 1900 1900 200...

Page 25: ...nd the water heater Boiler s maximum operating pressure and the maximum operating temperature are indicated in chapter 4 1 No minimum level of the amount of circulating water is required Damage can oc...

Page 26: ...delayed action fuse burner boiler and by an additional 6 3A delayed action fuse for each additional governor or module The quality of the supply must respect norm EN50160 voltage 10 max frequency 1 A...

Page 27: ...5 3265 Diameter FR mm 516 549 614 640 675 71 2 750 811 870 Burner connection Burner admittance diameter M mm 230 3 0 0 330 3 8 0 Burner tube lenght min max qN max max qN low NOx P mm 195 2 6 5 280 330...

Page 28: ...s oil tubes etc must not be attached to the boiler casing 6 7 3 1 Gas burner Observe the separate instructions of the burner The gas installation must be dimensioned in accordance with the gas flow ra...

Page 29: ...t flanges and cleaning covers remain accessible The chimney must be designed so that it is gas and pressure tight as well as moisture insensitive and acid resistant 6 8 3 Flue gas tubes Melbury C Depe...

Page 30: ...n pumps should be switched off and all ventilating valves opened so that the air in the system can completely escape The filling process is finished when the operating pressure has been reached 7 4 Pr...

Page 31: ...has been filled with insulation material Whether the boiler door is closed properly Whether the heating system has been filled up with water and completely vented Whether the thermostats are properly...

Page 32: ...onnect supply and burner plug Burner LED is on Press burner reset button No oil Gas pressure insufficient Add oil Call the gas board Overheat temperature LED is on Safety thermostat has come into oper...

Page 33: ...nance according to the recommendations given in the burner manual Check fuel oil level Clean boiler and chimney 9 2 Boiler cleaning Boiler should be cleaned by your chimney sweeper and engineer The cy...

Page 34: ...Melbury HE C 530 3000 32 We reserve the right to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 10 Spare parts 10 1 Melbury HE 530 895...

Page 35: ...40058 140058 140058 140058 Turbulators 3 120284 120284 120284 120284 120284 120285 Smoke tube brush 404 120236 120236 120236 120236 120236 120237 Key 119 160235 160235 160235 160235 160235 160235 Sigh...

Page 36: ...Melbury HE C 530 3000 34 We reserve the right to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 10 3 Melbury HE 1150 3000...

Page 37: ...oke tube brush 404 120237 120237 120238 120238 120238 120239 Key 119 160235 160235 160234 160234 160234 160234 Sight glass 117 171523 171523 171523 171523 171523 171523 Flat spring 108 122503 122503 1...

Page 38: ...nstruction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF Wessex House New Fields Business Park Stonsford Road Poole Dorset BH17 ONF Tel 01202662500 Fax 01202 662522 seNice hamworthy heatin...

Reviews: