7

Corridors with a width > 3 m:

in corridors (L-/ U-shaped) with a width of more than
3 m, these should be conceptually along the flanks
and seen as individual rooms. The resulting "rooms"
must be equipped with smoke detectors accordingly.

> 3 m

> 3 m

4a

>

3

m

> 3 m

> 3 m

4b

Note

Note that the requirements are not only valid for
corridors but also for rooms with these geometries
(e.g. corner rooms).

4.3.5 Standard rooms

• For pitched roofs with a roof pitch >20°, the

smoke detector must be installed at a distance
of at least 0.5 m and max. 1 m from the gable
peak, see Fig. 5a.

0.5 m

0.5 m

>20°

5a

• Note the following for rooms that only have a par-

tial roof slope: if the horizontal ceiling is less than
1 m wide, the smoke detector must be installed
on the roof slope as shown in Figure 5b.

>20°

max. 1 m

0.5

m

0.5

m

5b

• If the horizontal ceiling is wider than 1 m, the

smoke detector must be mounted centrally on it.

>20°

> 1 m

0.5 m

0.5 m

5c

• Roof pitches

20° should be treated as horizon-

tal ceilings. (See

4.3.3

.

Standard rooms

)

Summary of Contents for GS526

Page 1: ...Smoke Alarm GS526 Rauchwarnmelder 00 223842 D GB Operating Instructions Bedienungsanleitung...

Page 2: ...f any kind of damage the smoke detector must be replaced Draw up an escape plan in case of emergency see 6 1 for instructions The escape plan recommendation Warning of hearing damage The smoke detecto...

Page 3: ...om Child s room Bath room Corridor Smoke detector for minimum protection Smoke detector for optimal protection Installation locations with restrictions In buildings with several residential units smok...

Page 4: ...ork Construction work cleaning work with dust generation Strong electromagnetic effects Significant temperature fluctuations which can lead to condensation of the humidity in the smoke detector etc If...

Page 5: ...hen and water vapour can be excluded When installing the smoke detector near dishwashers washing machines ovens etc keep it at least 3 m away from these areas When installing the smoke detector near v...

Page 6: ...itchens that serve as escape routes Corridors and rooms with a width 1 m the ideal installation location is on the ceiling centrally between the walls Corridors with a width 3 m in corridors with a ma...

Page 7: ...rooms For pitched roofs with a roof pitch 20 the smoke detector must be installed at a distance of at least 0 5 m and max 1 m from the gable peak see Fig 5a 0 5 m 0 5 m 20 5a Note the following for r...

Page 8: ...s are higher than 0 2 m and the area of the individual ceiling panels is less than 36 m each the joists beams are not relevant and are to be seen as part of the ceiling The smoke detector can be insta...

Page 9: ...tach the smoke detector to the base plate affixed to the installation location by inserting the latching hooks into the openings provided and turning the smoke detector clockwise Check that the smoke...

Page 10: ...Mute mode in the case of a false alarm Warning Before activating mute mode clarify the cause of the alarm and make sure that there is no further danger Note Cigarette smoke will not normally trigger...

Page 11: ...ce the smoke detector with a new device Ensure that all specifications are met according to the installation location see 4 Installation In the event of structural recognisable changes check whether t...

Page 12: ...h red LED flash repetition of alarm scheme Temperature range 5 C 40 C 12 LED and acoustic signalling LED flashes every 40 seconds The smoke detector is working properly LED flashes every second and al...

Page 13: ...Installationshinweise Bei jeglicher Art von Besch digung ist der Rauchwarnmelder auszutauschen Erstellen Sie f r den Notfall einen Fluchtplan Hin weise dazu finden Sie unter 6 1 Der Fluchtplan Empfeh...

Page 14: ...rschriften f r die Installation 4 1 Allgemeine Hinweise F r die Mindestabsicherung wird empfohlen je einen Rauchwarnmelder in jedem Schlaf und Kinderzimmer sowie in Fluren die zu diesen R umen f hren...

Page 15: ...und Umgebungen neigen aufgrund ihrer typischen Nutzung m glicherweise beg nstigt zur Ausl sung von Fehlalarmen Darunter fallen St rfaktoren wie z B Wasser Koch und sonstige D mpfe Schwei L t Trenn un...

Page 16: ...eitig Fehlalarme durch K chen und Wasserdampf ausgeschlossen werden k nnen Halten Sie bei der Installation des Rauchwarn melders in der N he von Geschirrsp lern Waschmaschinen fen etc mindestens 3 m A...

Page 17: ...4 3 8 Wandmontage beschrieben zu bevorzugen Flure und R ume mit einer Breite 1 m Der ideale Montageort ist an der Decke mittig zwischen den W nden Flure mit einer Breite 3 m In Fluren mit einer maxim...

Page 18: ...3 5 Standard R ume Bei Spitzd chern mit einer Dachneigung 20 ist der Rauchwarnmelder in einer Entfernung von mind 0 5 m und max 1 m von der Giebelspitze anzubringen siehe Bild 5a 0 5 m 0 5 m 20 5a Be...

Page 19: ...er einzelnen Deckenfelder jeweils kleiner als 36 m sind die Unterz ge Balken nicht relevant und als Bestandteil der Decke zu sehen Der Rauchwarn melder kann auf einem Deckenfeld oder direkt auf dem Un...

Page 20: ...gen Sie den Rauchwarnmelder auf der an der Montagestelle angebrachten Grundplatte indem Sie die Rasthaken in die vorgesehenen ffnungen einf hren und den Rauchwarnmelder im Uhrzeigersinn drehen Kontrol...

Page 21: ...vieren kl ren Sie die Ursache f r den Alarm und vergewissern Sie sich dass keine weitere Gefahr besteht Hinweis Zigarettenrauch wird normalerweise den Alarm nicht ausl sen au er der Rauch wird direkt...

Page 22: ...Risse im Geh use aufweist Sollte dies der Fall sein ersetzen Sie den Rauchwarnmelder durch ein neues Ger t Stellen Sie sicher dass alle Vorgaben entsprechend des Montageorts siehe 4 Montage eingehalte...

Page 23: ...iederholung des Alarmschemas Temperaturbereich 5 C 40 C 12 LED und akkustische Signalisierung LED blinkt alle 40 Sekunden Der Rauchwarnmelder funktioniert ordnungsgem LED blinkt jede Sekunde und Alarm...

Page 24: ...corresponding companies Errors and omissions excepted and subject to technical changes Our general terms of delivery and payment are applied Hama GmbH Co KG 86652 Monheim Germany Service Support www h...

Reviews: