MAN1565-4
14
6.4
Links, and Settings
SW1
Except for the Zone Mimic Indicator Card in ZoneSense PLUS
FACP’s there can only be one (1) board / Card of each
type so the address on each board is set to 1.
Note:
There can be up to 8 remote Zone Mimic Indicator Cards so the address of each is set from 1 to 8 depending
on the actual number of LED Mimics in the system. The information at each location will be identical.
Address Setting
DIL Switch: ON = 1, OFF = 0
Address
1234
Address
1234
01
1000
05
1010
02
0100
06
0110
03
1100
07
1110
04
0010
08
0001
1
2
3
4
On
Figure 8: Example of Switch Set to 1
LK1 on Each Board
LK1 is the EOL Link and MUST be inserted on the last board on each communications bus. If not, communications
faults can occur.
Note:
Programming and the communication process allows the Main Card to identify the type of board it is
communicating with.