MAN1544-5
8
2.3
FireFighter Facility Controls and Indicators
Note:
Any of the buttons within the FireFighter Facility will act as a buzzer mute.
External Alarm Isolate
Is a dedicated control used to isolate (turn off) the “External Alarms”
output and is not over ridden by any other condition. The LCD Screen will display the isolate if
the ISOLATES / OUTPUTS menu is selected.
External Alarml Isolate
–
Amber Illuminated by the isolation of the “External Bell” output. This indicator is
integral with the “External Bell Isolate” button.
Warning System Isolate
Isolates (turns off) the “Warning System” output and is not o
ver ridden
by any other condition. The LCD Screen will display the WARNING SYSTEM is isolated if the ISOLATE /
OUTPUTS menu is selected.
Warning System Isolate
–
Amber Illuminated by the isolation of the ‘Warning System” output. This
indicator is integral
with the “Warning System Isolate” button.
Acknowledge
On Alarm the Alarm LED and Zone Alarm LED will flash and the Buzzer will sound.
By pressing Acknowledge the LED’s become steady, the Buzzer will be silenced and a zone/s can be Isolated
or Reset.
Alarm
–
Red: Alarm is a general fire indicator that flashes until all alarms have been acknowledged or
isolated. Once acknowledged it is lit steady until reset.
Reset
The Reset is used to return the control panel back to a normal state from the fire alarm
condition. The Reset button is not to be used for any other purpose and will not reset an isolated condition.
Fault
–
Amber Is a general fault indicator that flashes if a fault is present on any part of the system.
Isolate
Isolates or De - isolates a Zone which has been selected using the Zone Select Menu.
Inhibits Alarm and Fault signalling outputs but not LED indications generated by the corresponding zone.
Isolates all acknowledged alarms in a single operation and operates the fault buzzer if an isolate condition
still exists on the panel after 8 hours. The LCD screens below show an example.
Isolate
–
Amber Is a general isolate indicator that is illuminated if a Zone, Bell, Warning System or ACF is
isolated.