MAN1544-5
28
5.3.4
Outputs
To assign Zones that will activate the monitored outputs press
and a sub menu will be made
available for programming. The default condition for each output is all Zones will activate all outputs. The
sub menu consists off;
Outputs
Bell
Warn Sys
ACF
ASE
Alarm BGD
ALM1
BGD
ALM2
RST/BZ
To move through the sub menu use the
Move Right and
Move Left keys. For each output press
, then the
Move Left and
Move Right to select the Zones that will operate or not operate
that output. Pressing the
Move Up key will set the Zone to activate the output and the
Move Down key will set the selected Zone so it does not activate the output.
WARN SYS
12345678
WARN SYS
12........... 78
All 8 Zones Selected
Zones 1,2,7 and 8 Selected
Press
to Update the Program then Cancel to return to the Sub Menu and the
Move Right and or
Move Left keys to move through it. Repeat the above procedure to set or change the other Outputs as
required.
Set the
Reset / Buzzer output
option so as the output acts as a Reset or Buzzer function as per the system
design configuration.
RST / BZ
RESET
Screen Showing the Output Set to Reset
If the output is used set as a Reset or Buzzer function by using the
Move Up for Buzzer or
Move Down keys for Reset. Press
to update the program