MAN1544-5
21
4.2
Isolates
To display the number of Isolates press
to access the menus then
Move Left or
Move Right
to select the required menu. The number of isolates will be displayed for each step.
Zone [ Main Brd ]
Monitored Outputs
Relay [ Relay Brd ]
Sounder [ Sndr Brd ]
Zones 1 to 8 are
[ Main Brd ]
Relays 1 to 8 are
Sounders 1 to 8 are
Active or Isolated
Bell, Warn Sys ACF
Active or Isolated
Active or Isolated
ASE, Alarm, Fault
Only available if relays and or sounders are
installed
Note:
The Relay and Sounder Isolate Menus are only displayed if the boards are installed in the FACP and
set to active in the System Menu.
4.2.1
Main Control Board Zone, Relay Board or Sounder Board Isolates
Press
Enter
and use the
Move Left or
Move Right keys to select the Zone, Relay or Sounder
number then the
Move up to key isolate or
Move Down key to make active (set) the
required Zone, Relay or Sounder.
ZONES
X ISOL'D
ZONE 1
Active
ZONE 1
Isolated
Press
Enter
Select Zone Number
set,
Active or
Isolated
Note:
X denotes the Zone number, substitute Relay or Sounder for those menus.
If a Zone or Zones are Isolated the Isolate LED for that Zone and the common Isolated LED will be
illuminated. If a Relay or Relays, Sounder or Sounders are isolated only the common Isolate LED will be
illuminated. The Isolate can be deactivated by pressing ISOLATE / DE-ISOLATE while in the Output menu or
repeating the steps above to de-isolate (make Active) individual Zones.