Level 2 Access
At this level the operator is expected to have under gone training so as to be able to;
➢
Test crucial elements of the system and;
TEST
➢
Isolate dedicated facilities that may be in fault.
ISOLATE
In the Main Menu From FAULTS
Move Right for TEST
4.1
Tests
Press
Enter
to access the available menus
The available menus are;
Alarm Test
Fault Test
Walk Test Lamp Test
Battery Test
Sounder Test
Note:
The Sounder Test Menu is only displayed if it is installed and set to active in the System Menu.
To initiate one of the above tests press the
Move Right /
Move Left key to move through the
menu. Press
, then select the Zone by using the
Move Up and / or
Move Down keys
until the desired Zone number is displayed, press
to start the test.
4.1.1
Alarm Test
Once the test is commenced the Buzzer will turn on and off and the common Alarm and Zone Alarm LED’s
will flash. Press
,
the Buzzer will be silenced and the common Alarm and Zone Alarm LED’s will be
steady. Press
to return the panel to normal. The LCD will indicate the alarm has occurred and
then toggle to display the Zone and descriptor of that Zone.
ALRM TST
ZONE 1
ALARM
OCCURRED
Z1 : LOBBY
Figure 10: Alarm LCD Sequence
Note:
If a Zone has been programmed to be;
NON LATCHING the panel will only go into alarm for 5 seconds and then automatically reset.
Self Resetting ( SREST 60) the panel will go into alarm for 60 seconds and then automatically reset.