GRUPAd.o.o.
34
Outdoor units(combination)
Norminal condition: indoor temperature (cooling): 27
0
CDB/19
0
CWB, indoor temperature (heating): 20
0
CDB/14.5
0
CWB
Outdoor temperature(cooling): 35
0
CDB/24
0
CWB, outdoor temperature(heating): 7
0
CDB/6
0
CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
Noise level(dB(A))
Equivalent HP
Model
Combination mode
Nominal cooling capacity(KW)
Nominal heating capacity(KW)
Heating capacity at low temp.(KW)
Power source
Operating/Max. current(A)
Operating/Max. consumption(kw)
Cooling
Operating/Max. current(A)
Operating/Max. consumption(kw)
Hea
ting
Electrical characteristics
Power consumption when heating at low temp.(kw)
Exterior dimensions (mm)
Weight (Kg)
Exterior colour
Compressor type
Outdoor airflow (m
3
/h)
Refrigerant (R410A) charge (Kg)
Gas piping(mm)
Liquid piping(mm)
Equipoise/Oil equalization piping(mm)
Piping dimension
3N~, 380~400V, 50Hz
18
AV18NMVERA
AV08+AV10
50.6
56.5
46.8
20.9/26.1
12.64/15.79
22.9/27.1
13.86/17.05
12.3
1.4
990*750*1750
+990*750*1750
470
ivory
scroll
20000
20
61
Output power of outdoor motor(KW)
28.58
15.88
9.52
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
20
AV20NMVERA
AV10+AV10
56.0
63.0
51.2
24.4/31.2
14.72/18.90
26.4/31.6
15.94/20.4
13.46
1.4
990*750*1750
+990*750*1750
470
ivory
scroll
20000
20
61
28.58
15.88
9.52
compressor
oil type
MEL32
oil charging amount
3 litre with compressor, additional charging 1 litre to gas-liquid segregator
HNB71FB-YJHC, Mitsubishi Electric