12. Wiring design
Warning :In European Market :local 3 phase isolator (power switch) must be fitted locally to
the unit (Legal requirement for EU).
For other area, pls. comply with local regulation requirement.
Electric wiring should be executed by the specialized well-trained person.
Warnings:
A. Do not take the other wire except for copper wire as the power cable.
B. All indoor/outdoor units must be connected with the earthing wire of power cable. The earthing wire can not be
connected onto the earthing wire of coal gas pipe, water pipe, lightning rod, or telephone. Or the electric shock or
fire will occur.
C. Must install the leakage breaker and the over current breaker, or electric shock will occur.
D. Before finishing electric installation, do not electrify the unit.
E. Indoor and outdoor use their individual power source. All indoors use one power source.
F. The communication wire and the power cable must be individual and can not use one multi-core cable, or
the communication wire will be interfered to cause abnormal.
Note: When one wired controller controls multiple indoors, the connected indoor units must use the
common phase of power source, or the communication will be abnormal.For example, the power source
is L1,L2,L3,and N, all the indoor units must use L1/N or L2/N or L3/N.
1. Wiring system:
(1) Power wiring figure
leakage breaker
L1 L2 L3 N
outdoor 1
power source: 3PH, 380V, 50Hz
L N
indoor 3 (non wall mounted unit)
power source: 1PH, 220V, 50Hz
L N
TW1
1 2
Tw3
indoor 1 (wall mounted unit)
power source: 1PH, 220V, 50Hz
over current breaker
leakage breaker
L1 L2 L3 N
outdoor 2
power source: 3PH, 380V, 50Hz
over current breaker
leakage breaker
L1 L2 L3 N
outdoor 3
power source: 3PH, 380V, 50Hz
over current breaker
leakage breaker
over current breaker
L N
TW1
1 2
Tw3
indoor 2 (wall mounted unit)
power source: 1PH, 220V, 50Hz
leakage breaker
over current breaker
over current breaker
leakage breaker