89
Note:
1. Please follow the national electrical standards, all provided parts, raw materials must comply with local laws
and regulations. And please professional electrician installation.
2. Power supply must use the rated voltage and air conditioning unit dedicated power supply, power fluctuations
in the power supply ratio of less than 2%, and were designed indoor unit, outdoor machine dedicated power.
3. The power cord should be reliably fastened to prevent the terminals from being stressed. Please do not force
the power cord.
4. The power line diameter should be large enough, the ground wire should be reliable, should be connected to
the building's special grounding device.
5. The air switch and earth leakage switch that can be cut off the entire system must be installed. Air switch
should also have a magnetic trip and thermal trip function to ensure that short circuit and overload are
protected, Should use "D" type circuit breaker.
6. Do not add the phase-connected capacitor to prevent overheating of the capacitor due to high frequency
waves.
7. Please follow the instructions in accordance with the requirements of the power cord connection, so as to avoid
a security incident.
8. The unit must be reliably grounded to meet the relevant requirements of GB 50169.
9. All electrical installations must be carried out by professionals in accordance with local laws, regulations and
corresponding instructions.
Power
Outdoor unit leakage protection switch and circuit breaker
Model
Power
source
Maximum
load current
(A)
Circuit
breaker
Each module
circuit breaker
Leakage current
(mA)
response time(S)
Minimum
sectional area of
power line (mm
2
)
Minimum sectional
area of earthing
line (mm
2
)
AV08IMVURA
3N~,
380-415V,
50/60Hz
20.3
25
25
30mA, below0.1s
6
4
AV10IMVURA
21.8
25
25
6
4
AV12IMVURA
23.3
32
32
10
4
AV14IMVURA
27.7
40
40
10
4
AV16IMVURA
32.4
40
40
10
4
AV18IMVURA
36.1
50
50
16
6
AV20IMVURA
42.4
63
63
16
6
AV22IMVURA
48.1
63
63
25
10
Outdoor 1
Outdoor 2
Outdoor 3
Outdoor 4
Circuit breaker
Power control cabinet
Circuit breaker
Circuit breaker
Circuit breaker Circuit breaker
Note:
1. Main FUSE in appliance: 63A. The fuse shall be replaced by the professional person.
2. Select the power supply cabling of each outdoor unit from the following specifications: Cable 5-core, in conformance
with design H07 RN-F or 60245 IEC 66. The operating temperature can not be greater than its specified value.
10.4. Electric wiring and the application
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...