88
• HP gas pipe, Suction gas pipe and liquid pipe should be heat insulated separately.
• The material for HP gas pipe and Suction gas pipe should endure the high temperature over 120°C. That for
liquid pipe should be over 70°C.
• The material thickness should be over 10mm, when ambient temp. is 30°C, and the relative humidity is over 80%,
the material thickness should be over 20mm.
• The material should cling the pipe closely without gap, then be wrapped with adhesive tape. The connection wire
can not be put together with the heat insulation material and should be far at least 20cm.
Heat insulation
• In operation, the pipe will vibrate and expand or shrink.
If not being fixed, the refrigerant will focus on one part to cause the broken pipe.
• To prevent the stress concentration, fix the pipe for every 2-3m.
Fix the refrigerant pipe
Note:
• To prevent the oil going into the pipe, please use the special tool for R410A, especially for gauge manifold and
charging hose.
•
Mark the refrigerant type in different colour on the tank. R410A is pink.
• Must not use the charging cylinder, because the R410A will change when transferring to the cylinder.
• When charging refrigerant, the refrigerant should be taken out from the tank as liquid state.
•
Mark the counted refrigerant volume due to the distributing pipe length on the label.
GWP: 2088
The product contains fluorinated greenhouse gases and its functioning relies upon such gases.
Connection wire
over 20cm
Adhesive tape
Heat insulator
Suction gas pipe
Liquid pipe
HP gas pipe
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...