83
Outdoor pipe dimension
24~44HP
a Liquid pipe
b Suction gas pipe
c HP gas pipe
d Liquid pipe
a
b
c
e Suction gas pipe
f HP gas pipe
46~66HP
g Liquid pipe
d
a
e
b
f
c
h Suction gas pipe
i HP gas pipe
68~88HP
The pipe "a, b, c, d, e, f, g, h, i" should be confirmed as to the below table
Unit pipe spec and connection method (unit: mm)
A. Outdoor unit
Total outdoor capacity before gather
pipe (kW)
Suction gas pipe (a,d,g)
(mm)
HP gas pipe (b,e,h)
(mm)
Liquid pipe (c,f,i)
(mm)
45.0
φ28.58
φ25.40
φ12.70
50.4~80
φ28.58
φ25.40
φ15.88
85~95.4
φ31.80
φ28.58
φ19.05
100.8~156.8
φ38.10
φ34.90
φ19.05
162.4~184.5
φ41.30
φ38.10
φ19.05
191.0~236
φ44.50
φ41.30
φ22.22
241.5~248.0
φ50.80
φ44.50
φ25.40
Model
HP gas pip
Suction gas pip
Liquid pipe
Diameter
(mm)
Connection
method
Diameter
(mm)
Connection
method
Diameter
(mm)
Connection
method
AV08IMVURA
Ø19.05
Flared
Ø19.05
Flared
Ø9.52
Flared
AV10IMVURA
Ø19.05
Ø22.22
Braze
Ø9.52
AV12IMVURA
Ø22.22
Braze
Ø25.4
Ø12.7
AV14IMVURA
Ø22.22
Ø25.4
Ø12.7
AV16IMVURA
Ø25.4
Ø28.58
Ø12.7
AV18IMVURA
Ø25.4
Ø28.58
Ø15.88
AV20IMVURA
Ø25.4
Ø28.58
Ø15.88
AV22IMVURA
Ø25.4
Ø28.58
Ø15.88
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...