81
Pipe diameter
D
Bending radius
R
Vertical heigh
H
Ø19.05
≥31
≤150
Ø22.22
≥31
≤150
Ø25.4
≥45
≤150
Ø28.58
≥45
≤150
Ø31.8
≥60
≤250
Ø38.1
≥60
≤350
Ø41.3
≥80
≤450
Ø44.5
≥80
≤500
Ø50.8
≥90
≤500
Ø54.1
≥90
≤500
R
H
D
R
H
D
In order to avoid damage to the pipe, the size of the return bend is referred to as the drawing.
Compressor oil will flow into
the lowest unit
Proper installation
Wrong installation
Oil return bend
The height of the vertical
section see schedule
requirements