214
Failure code
Outdoor
digital
display tube:
119-1, 2
Indoor wired
controller77
Indoor unit LED status
LED5
Failure description:
Current detecting circuit abnormal of com-
pressor module
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Failure diagnosis and troubleshooting
MRV 5-RC series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check if the current
sensor is reversely
connected and U and W is in
reverse direction.
◆
Check if the current
sensor is in reverse
direction. (the arrow
on sensor points at the
compressor)
◆
Check if the inverter
board is well.
◆
Check if the current
sensor is well.
3. Abnormity confirmation
conditions
The current detection sensor
of inverter control board
is in abnormal conditions,
disconnected or connected
incorrectly.
4. Possible causes
◆
The inverter board and
current sensor is anti-
connected or the current
sensor is in incorrect
direction.
◆
The inverter board or
current sensor is damaged.
Check if the inverter module is
connected to the three phase lines,
U (red), V (white) and W (black)
correspondingly on compressor?
Check if the current sensor
detects the current of U phase
and W phase?
Check if the screen printed
arrow on current sensor
points to the compressor?
Check if the harness terminal
of current sensor is connected
correspondingly to the inverter
controlling board? Is the
connection reliable?
After power on and before
operation, test the DC
voltage between the second
pin (black, earth wire) and
third pin (brown, signal wire)
of the wiring harness terminal of
the two current sensors,
confirm if the signal voltage
is within 3V±0.2V?
Correct the connection in
accordance with the wiring
diagram.
Correct the connection in
accordance with the wiring
diagram and ensure negative
phase and phase loss are not
found.
Correct the connection in
accordance with the wiring
diagram.
Correct the connection in
accordance with the wiring
diagram.
Replace the current sensor
with abnormal signal voltage.
Y
Y
Y
Y
N
N
N
N
N
To be continued
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...