158
SW1
SW2
SW3
function
Digital tube LD1 ~ 4 display
Control
range
15
(
F
)
0
2
In the same machine drive
off control selection
0- machine automatic control according to the
group number, all within the machine with
1- drive,
2- all in each machine control, drive off with ban
Group
class
(physical
master
unit is
valid)
15
(
F
)
1
2
Selection of low temperature
automatic operation control
for indoor unit
0- within the machine automatic control,
1- all within the machine is valid,
2- all the inside of the machine is invalid
15
(
F
)
2
2
Pipe length selection
0
:
short pipe length;
1
:
middle pipe length
;
2
:
long pipe length
15
(
F
)
3
2
Defrosting conditions
selection
0- normal area,
1- area easy to frost
15
(
F
)
4
2
Operation mode priority
0- first open priority
;
1- after opening priority
2- cooling priority
;
3- heating priority
15
(
F
)
6
2
Heating limit when
Outdoor temp
Over 25 degree
0-shows no limitation,
1-shows limitation
15
(
F
)
7
2
Silent running option
0-without silent operation
,
1- silent operation 1
,
2- silent operation 2
,
3- silent operation 3
,
4- silent operation 4
15
(
F
)
8
2
snow-proof operation setting 0-without snow-proof operation
,
1- without snow-proof operation
15
(
F
)
9
2
When the main outdoor
machine is running, the
choice of the operation of the
wind turbine is stopped.
0-stop
,
1-run
15
(
F
)
12
(
C
)
2
Power limit operation control
mode selection
0- By E2 value,
1- By external contact DRM
15
(
F
)
13
(
D
)
2
Power output ratio selection
(E2 control method is valid)
Maximum capacity to allow the maximum
number of files, a total of 11 stalls, 0 stalls for
10, 0%, 100%
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...