<Note>
• For pipe welding, do not use antioxidant, for its residue may cause tube blocking and component fault.
• For pipe welding, do not use flux. If the flux is chlorine product, it will corrode the tube; if it contains fluorine, it will
even cause detrimental effects to the refrigerant system, such as refrigerant oil deterioration. Please do not use
phosphor copper for welding material (BCup-2).
Selection of piping dimensions
Select refrigerant branching dimensions between outdoor units and valve box, between valve box and indoor units
according to the following connection examples 1 and 2 and Tables 5-7.
Connection example 1: Connect an indoor unit to the downstream of the valve box
Connection example 2: with branching in the downstream of the valve box
(
) For dimensions of the pipes to the downstream of the valve box, see the table 3. Use the attached pipes for
connection in the way shown in Pipe connection according to the pipes dimensions and diameters for indoor unit
connection selected in Table 2.
<Table 5> Total capacity and pipe dimensions (mm) of the indoor units
Total capacity of the
indoor units
Q (kW)
Pipe dimensions (OD × minimum wall thickness)
Upstream
Downstream
Suction gas
pipe
High pressure gas
pipe
Liquid pipe
Gas pipe
Liquid pipe
Q<16.8
Ø15.88×1.0
Ø12.7×1.0
Ø9.52×0.8
Ø15.88×1.0
Ø9.52×0.8
16.8≤Q<22.4
Ø19.05×1.0
Ø15.88×1.0
Ø19.05×1.0
22.4≤Q<28.0
Ø22.22×1.2
Ø19.05×1.0
Ø22.22×1.2
Upstream
Suction gas pipe
Gas pipe
Liquid pipe
HP gas pipe
Liquid pipe
Downstream
To outdoor unit or
refrigerant branching suite
Indoor unit
Valve box
Select from Table 2 according to the
capacity type of the indoor units
Select from Table 1 according to
total capacities of the indoor units
connected in the downstream
Valve box
To outdoor unit or
refrigerant branching suite
Select from Table 1 according to total capacities
of the indoor units connected in the downstream
Select pipe dimensions of the refrigerant branching suite and its components in the indoor
unit according to the specifications or technical data provided together with the outdoor unit.
Upstream
Downstream
Refrigerant branching suite
Suction gas pipe
HP gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Indoor unit
Indoor unit
Indoor unit
Summary of Contents for MRV 5-RC AB052MAERA
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...