– 22 –
Internal Condensate Removal Control
Internal Condensate Removal Control (AZ6500 Only)
The Internal Condensate Removal (ICR) function will be utilized to drip the condensation, from the
base pan, onto the indoor coil to evaporate it when the compressor is running during the heat pump
operation.
During heat pump operation, the ICR system pumps condensate water from the Zoneline base pan into
a collector tray, positioned above the indoor coil.
The collected condensate will then drain from the tray onto the warm indoor coil where it is evaporated
into the room atmosphere. If an excessive amount of condensate water is pumped to the indoor side,
the excess amount is routed back to the outdoor portion of the Zoneline base pan.
The ICR function works in tandem with heat pump compressor operation, except in case of Reverse
Cycle Defrosting.
The ICR function can be utilized in the Class 2 mode.
ICR Pump Operation
33°F
28°F
ICR Pump
3 min.
On
On
Outdoor Air
Temp.