Table 5.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 2,000 ft
Number of
90° Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
045
070
090
110
1
20
15
n/a
n/a
81
66
44
24
115
115
93
58
138
137
118
118
2
15
10
76
61
39
19
110
110
88
53
133
132
113
113
3
10
n/a
71
56
34
14
105
105
83
48
128
127
108
108
4
n/a
66
51
29
n/a
100
100
78
43
123
122
103
103
5
61
46
24
95
95
73
38
118
117
98
98
6
56
41
19
90
90
68
33
113
112
93
93
7
51
36
14
85
85
63
28
108
107
88
88
8
46
31
n/a
80
80
58
23
103
102
83
83
9
41
26
75
75
53
18
98
97
78
78
10
36
21
70
70
48
13
93
92
73
73
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.
Table 5A.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 2,001 - 10,000 ft
Number of 90°
Elbows Used
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
81
35
20
n/a
115
110
67
53
138
137
118
118
2
76
30
15
110
105
62
48
133
132
113
113
3
71
25
10
105
100
57
43
128
127
108
108
4
66
20
n/a
100
95
52
38
123
122
103
103
5
61
15
95
90
47
33
118
117
98
98
6
56
10
90
85
42
28
113
112
93
93
7
51
n/a
85
80
37
23
108
107
88
88
8
46
80
75
32
18
103
102
83
83
9
41
75
70
27
13
98
97
78
78
10
36
70
65
22
n/a
93
92
73
73
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.