13. Unit Operating Range and Service Condition
■
Unit Service Conditions
1. Unit operating range
Cooling
Ambient
temperature
(°C)
Water outlet temperature (°C)
Water outlet temperature (°C)
Ambient
temperature
(°C)
20
20
-10
-10
25
25
-5
-5
30
30
0
0
35
35
5
5
40
40
10
10
45
45
15
15
20
20
25
25
30
30
35
35
50
50
55
55
45
45
40
40
485
7.5
12.5
10
15
Heating
2. Service conditions
Item
Contents
Power supply voltage
Within ±10% of the rated voltage
Power supply frequency
Within ±1% of rated frequency
Phase imbalance
Voltage difference between two phases of the power supply is less than
2% of the rated voltage
Chilled water flow
Within ±30% of the rated water flow
Chilled water pressure
Below 0.7MPa
Chilled water quality
Free from corrosive copper, iron, dissolved matters of welding materials
Installation site
Provided with snow protection and ventilation
Ambient temperature
Refer to the above diagram (operating range).
Relative humidity
Below 90%
Optimal operating temperature 12°C for cooling, 40°C for heating
Note:
the operating range based on GB/T 18430.1, and the rated water flow is obtained from lab. If theunit exceeds the
maximum operating range, it only can run for a short time, otherwise the unit may send
fault alarm or be damaged.
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...