16
9. Electric Characteristics
Model
Outdoor Unit
Power Supply Compressor
OFM
Hz
Voltage Phase Min. Max. MCA
MFA
MSC
kW
FLA
AU082FYCRA(HW) 50Hz
220~240V
1Ph 198V 264V 21.3
32
4.2
0.18
0.8
AU112FYCRA(HW) 50Hz
220~240V
1Ph 198V 264V 24.3
32
8.5
0.18+0.18 0.8+0.8
AU162FYCRA(HW) 50Hz
220~240V
1Ph 198V 264V 31.7
40
14
0.18+0.18 0.8+0.8
Remark:
MCA: Min. Current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A)
kW: Rated Motor Output (kW)