No. 0010577688

CASSETTE TYPE AIR CONDITIONER

Operation & Installation
Manual

AB072XCEAA
AB092XCEAA
AB122XCEAA
AB142XCEAA

Please read this operation manual before using the air conditioner.

Please keep this manual carefully and safely.

Большая библиотека технической документации

http://splitoff.ru/tehn-doc.html   

каталоги, инструкции, сервисные мануалы, схемы.

Summary of Contents for AB072XCEAA

Page 1: ...IR CONDITIONER Operation Installation Manual AB072XCEAA AB092XCEAA AB122XCEAA AB142XCEAA Please read this operation manual before using the air conditioner Please keep this manual carefully and safely http splitoff ru tehn doc html ...

Page 2: ...t Name Safety Precautions Maintenance When Trouble Happens Customer Need to know Installation Tools Installation Procedures Troubleshooting Failure code Check and Test Run 1 2 3 4 5 6 7 8 9 10 11 12 13 19 20 21 22 23 http splitoff ru tehn doc html ...

Page 3: ... require specialized waste disposal The valuable materials contained in a air conditioner can be recycled Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal c...

Page 4: ... shouldbeH05RN F3G 0 75 1 5 mm2 Thesignalcableshouldbe H05RN F2x 0 75 1 5 mm2 AllthecablesshallhavegottheEuropean authenticationcertificate 1 The waste battery should be disposed properly When throw away the waste batteries please perform in accordance with the local regulation 2 The indoor unit installation height is at least 2 5m certificate 5 The power cord should be self provided and it should...

Page 5: ...m temperature is close to the setting temperature in cooling mode In heating mode the compressor stops when the room temperature is at setting temperature and fan turns into low speed or stops In Dry mode fan speed will be automatically adjusted Remote Control There is a telecommunication interface for remote control on the operation panel of the indoor unit After the peripheral equipment have bee...

Page 6: ...e suddenly occurs while the air conditioner is working it will resume the previous working state when the power is supplied again Setting Method When the remote controller is on excluding timer mode and fan mode press the SLEEP button on the remote controller 10 times within 5 seconds and after the buzzer sounds 4 times the air conditioner will enter the state of auto restant function Cancel Metho...

Page 7: ...tton on the remote controller Air Inlet Grille Air Filter Inside of the Inlet Grille Operating Control Panel Remote receiver Compressor Lamp TIMER Lamp OPERATION Lamp Power Lamp Emergency switch 1 2 3 4 5 COMP TIMER OPER POWER 1 2 3 4 5 Operating Control Panel 6 6 http splitoff ru tehn doc html ...

Page 8: ...the unit needs maintenance and repair call dealer to handle it Don t put figures or any other things into the inlet outlet and swing louver while the conditi oner is in operation Call the dealer to take measures to prevent the refrigerant from leaking Switch off In such case to continue using the air conditioner will damage the conditioner and may cause electrical shock or fire hazard Incorrect ma...

Page 9: ...y after power supply is cut off to keep from shock or hurt Otherwise may cause shock Connect earthing wire Earthing wire should not be connected to the gas pipe liquid pipe lightning rod or phone line incorrect earthing may cause shock Use discharge pipe correctly to ensure efficient discharge Incorrect pipe usage may cause water leaking Air conditioner can t be be installed in the environment wit...

Page 10: ... outdoor unit Clean with hot wet cloth and neutral detergent then wipe with dry cloth Do not use too hot water over 40 C which may result in fading and deforming Do not use insecticide and chemical washing agent Fixing nolt lock filter corner grille edge take out the grille press the locks As the figure press the two locks on air inlet grille vertically and make it move to grille then rise it up 4...

Page 11: ... there is no obstacle at the air inlet and air outlet of both indoor and outdoor unit to avoid reducing the working efficiency Be sure to install the air filter ensure that the air filter is not dirty Otherwise may result in machine damages or cause malfunciton due to dust inside the unit To protect compressor when starting in HEAT mode please turn on the power supply switch for 12 hours before st...

Page 12: ...oom Sunlight direct into the room Too crowed in the room Cold air blown out when heating When the air conditioner does not operate properly after you have checked the above mentioned items or when following phenomenon is observed stop the operation of the air conditioner and contact your sales dealer The fuse or breaker often shuts down Water drops off during cooling or drying operation There is a...

Page 13: ...ing installation place After installation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature Too cool or hot is not good for your health Furthermore it will result in excessive consumption of electric power Optimal temper ature Effectively use t...

Page 14: ...age detector or soapy water 11 Band tape 12 Scraper 13 Refrigerant oil The installation tools listed in the following sheet can be used as required The following parts mentioned in this manual are the installation accessories we prepared Symbol Parts Name Adhesive tape Pipe clamp Connecting hose Drainage hose Non hydroscopic heat insulating material Gypsum powder Installation Tools http splitoff r...

Page 15: ...re than 1m away from television and radio to avoid disturbing television and radio 10 Easy for maintenance 2 Installation Preparation 1 Position of ceiling opening between unit and suspending bolt front view of unit 2 Prepare all piping refrigerant water drainage and wires connection wire of remote controller indoor unit connection wires to the indoor unit before installation in order to connect i...

Page 16: ...e nut and washer at both end of the bracket to secure it firmly Water pump and floating switch is installed inside indoor unit check four corners of the unit for its lever using horizontal comparator or PVC tube with water If unit is tilting against the direction of water drainage problem may occur on floating water leakage In the case of existing ceiling 1 Install unit temporarily 2 Adjust the he...

Page 17: ...ulation Insulate drainage hose in the room 5 Cautions for the water drainage lifting pipe Installation height of water drainage lifting pipe shall be less than 280mm There should be a right angle with unit 300mm from unit Note The slope of water drainage hose shall be within 75mm make the drainage plug not to bear excessive force If several water hoses join together of as per following procedures ...

Page 18: ... and other two and tighten the four screws 5 Connect the wires of synchro motor 6 Connect the wire of signal 7 If no response of remote controller check whether the wiring is correct restart remote controller 10 seconds after shut off power supply Panel limitation board installation 1 Install the panel board in the direction shown in the figure 2 The incorrect direction will result in water leakag...

Page 19: ...pe 9 52mm 6 35mm Fit the nut on and fasten 2 Pipe cutting and expanding Must remove burrs if cut pipes with pipe cutter Expand flare after insert the pipe expander Liquid pipe Diameter of pipe Dimension A mm 1 0 1 2 6 35mm 1 4 Gas pipe 1 0 1 8 9 52mm 3 8 Correct Incorrect Deflection Crack occurs Broken Incomplete Over outward A Pipe expander 3 The maximum length and drop height of connecting pipe ...

Page 20: ...service port into the projection of charge hose low for gauge manifold Then connect the projection of charge hose center for gaugemanifold into vacuum pump To use vacuum pump CAUTION If the refrigerant of the air conditioner leaks it is necessary to make all the refrigerant out then charge the liquid refrigerant into air conditioner according to the amount marked on the nameplate 2 Open 4 Purging ...

Page 21: ...or unit on the installation bracket firmly using bot M10 and nut and keep it on horizontal level When installing on the wall or on the roof fix the bracket firmly to prevent earthquake or storm Be sure to use rubber damping cushion to reduce unit vibration 2 Installation of drain elbow 3 Connection of outdoor piping Connect the connecting pipe according to the piping connection method 4 Confirm th...

Page 22: ...orbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the suddenly cooled indoor air is blown out Automatically switch into FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it sometimes auto matically switched into the FAN mod...

Page 23: ...m atically stops Water or vapor generated from the outdoor unit during heating This happens when the frost accumulated on the outdoor unit is removed during defrosting operation Defrosting operation Please check the following things about your air conditioner before making a service call Unit fails to start Is the power supply switched on Power supply switch is not in ON position Is city supply po...

Page 24: ...usly Sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously CT check abnormal 3 times in 30m High pressure switch acts 3 times in 30m Fault phase short of phase out of balance greatly Communication abnormal for more than 4m continuously Communication abnorm...

Page 25: ...nal block firmly Is the wiring of indoor and outdoor unit secured firmly Is the drainage hose arranged correct Is the earthing wire connected firmly Is the power supply voltage conformed to the electrical regulation Any noise Is the display on the control board LCD correct Cooling normal Does the indoor temperature regulator work normally For the power supply L shall be connected to the live wire ...

Page 26: ...GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com http splitoff ru tehn doc html ...