>a__WcU[S^ <[c >a`V[e[a`Wc
-39-
sensor abnormal
short circuit for more than
2m continuously
13 0D 31D
Solenoid valve
abnormal
Solenoid valve act
incorrectly 3 times
continuously
○
14 4C 15D
Discharging
temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
○
15
05
17D
EEPROM abnormal
EEPROM data missing
Run as the
default
value
16 54 26D
Pressure
abnormal(low
pressure)
Low pressure switch acts in
normal running
○
17 50 15D
Compressor
overheat
the
discharging
temperature is higher than
120degree
Resumable
if lower
than
100degree
18
0C
23D
Abnormal mode
Indoor operation mode is
different with the running
indoor unit.
○
19 4B 18D
Outdoor coil
B(suction temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
○
20 4D 15D
Outdoor
discharging
B(oil temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
○
21
32
07D
Power module failure Power module overheat, or
over current, or short circuit
※
22
54
08D
No
load
Sensor abnormal or the
compressor not start up
※
○
shows resumable fault,
※
shows it is not resumable fault.
Setting address method:
The address setting can be realized by setting indoor PCB.
If you use the group control function, there should be a master unit and 15 sets of slave units.
For the master unit, the SW5-3 should be at “ON”. For the slave units, the SW5-3 should be
at “OFF”.
Please refer the below table,
Indoor
unit
address
SW1-4 SW1-3 SW1-2 SW1-1
1 OFF OFF OFF OFF
2 OFF OFF OFF ON
Summary of Contents for AB072XCBAA
Page 21: ... a__WcU S c a V e a Wc AU84NXTBAA 66 33 1 23 4 43 33 61 2 3 160 2 15 3 52 21 ...
Page 138: ... a__WcU S c a V e a Wc AU282XHBAA AU422XIBAA PCB printed diagram 138 ...
Page 141: ... a__WcU S c a V e a Wc AU84NXTBAA PCB printed diagram 141 ...
Page 144: ... a__WcU S c a V e a Wc AB AE AD units PCB printed diagram 144 ...
Page 149: ... a__WcU S c a V e a Wc AF07 142XCBAA PCB printed diagram 149 ...
Page 180: ...MEMO Commercial Air Conditioner ...