 Iron Filter Sizing Formula

Iron Filter and Potassium Permanganate Feeder Installation Guide

The iron filter may be programmed to regenerate every one to twelve days. Select the frequency based on the amount of 

iron in the water and the number of people in the household. 

For optimum performance, program the water softener to 

regenerate first, followed by the Iron Filter.

Example:

 Softener 1:00am; Iron Filter 3:00am.

Regeneration Cycle Frequency Worksheet

This table will help you determine how often the iron filter will need to regenerate.

Important:

 The iron filter is capable of treating a combination of undesirable constituents in the water (iron, manganese, 

and/or hydrogen sulfide). However, the filter must be applied within the operating limits stated in the 

Filter Specifications

 in 

this manual. Failure to comply with these specifications will degrade performance and possibly cause the control valve to 

malfunction.

Note:

 The iron filter should be installed after the pressure tank or water meter and before the water heater or any water 

softener appliance, unless otherwise recommended. See Figure 6. A minimum 3/4-inch pipe is required for proper function 

of the filter. Examine the inlet piping to make sure the pipe is not plugged with lime or iron. If the piping is plugged, it must 

be cleaned or replaced.

Determine Monthly Usage

This table will help you determine how much regenerant the iron filter will use each month.

Water

Example

Total Iron

___ ppm (mg/L) x 1 =

___ ppm (mg/L)

3.5 ppm (mg/L) x 1 =

3.5 ppm (mg/L)

+ Manganese*

___ ppm (mg/L) x 3 =

___ ppm (mg/L)

0.2 ppm (mg/L) x 3 =

0.6 ppm (mg/L)

+ Sulfur

___ ppm (mg/L) x 5 =

___ ppm (mg/L)

1.0 ppm (mg/L) x 5 =

5.0 ppm (mg/L)

= Total compensated ppm

___ ppm (mg/L)

9.1 ppm (mg/L)

x Gallons per day for one 

person

75 gallons (284 L)

75 gallons (284 L)

= ppm per person per day

=

___ ppm (mg/L)

682.5 ppm

x Number of people in house-

hold

____ people

4 people

= Daily ppm capacity

___ ppm (mg/L)

2730 ppm

Iron filter capacity

=

10,000 ppm

10,000 ppm

÷ Daily ppm requirements

=

____ ppm

2730 ppm

= Frequency of regeneration

____ days

3.6 days

Set regeneration frequency

@

____ days

3 days

* If manganese is unknown, multiply the iron and sulfur total by 1.15 to adjust total compensated ppm.

Water

Example

Total days per month

____ days

30 days

÷ Frequency of regeneration

____ days

3 days

= Regenerations per month

____ regenerations

10 regenerations

x 4 oz (118 g) per regeneration = oz 

KMnO4 per month

____ oz

4 oz (118 g) x 10 regenerations = 40 oz (1.1 kg)

÷ 16 = lb per month

____ lb

40 oz (1.1 kg) ÷ 16 oz/lb (1 kg/kg) = 2.5 lb (1.1 kg)*

Figure 6: Iron Filter and Potassium Permanganate Feeder Placement

Step 1

Step 2

Install Filter

A.

 

Follow steps 1–3 of Installation Steps and Start-Up Procedures.

B.

 

Instead of connecting the brine tank, connect the potassium permanganate feeder as outlined below.

Unpack Feeder

A.

 

Remove feeder from shipping carton.

B.

 

Read the instructions in red, remove the label from the feeder, and discard it into the shipping carton.

C.

 

See Figure 6 for feeder placement.

D.

 

Remove the cover and set it aside.

E.

 

Pull up on the brine well cap to remove the safety shutoff assembly. Remove the rubber band from the 

air check/draw tube float rod assembly and replace the safety shutoff back into the brine well.

F.

 

Remove the plastic bag containing the three stainless steel screws and the 3/8-inch tubing.

Summary of Contents for WATERMAX SIGNATURE Series

Page 1: ...Water Conditioning Appliance SIGNATURE SERIES Owner s Manual and Installation Guide Version 1 0...

Page 2: ...ing these substances in the appliance specifications other special treatment of the water supply must be used to remove these substances before they enter this product Otherwise Hague Quality Water In...

Page 3: ...s potassium chloride in place of water conditioner salt A Hague dealer should be contacted before a switch is made to a salt substitute If potassium chloride is used in place of salt the technician mu...

Page 4: ...0 F 4 49 C Drain Drain the appliance to an appropriate drain such as a floor drain or washer drain that will comply with all local and state plumbing codes To prevent back siphoning provide an adequat...

Page 5: ...should make the shortest run to the suitable drain C The drain line may be elevated up to 8 feet 2 4 meters from the discharge on the appliance as long as the water pressure in your system is 40 psi...

Page 6: ...old water faucet to depressurize the lines 3 Close the faucet to eliminate any siphoning action 4 Repair all leaks 5 Turn on the water supply 6 Place the bypass in the Service position to slowly fill...

Page 7: ...jectionable concentrations of ferrous iron or sediment are present Because the blending valve is mixing raw water with softened any ferrous iron or sediment in the raw water will also be blended and r...

Page 8: ...ce Settings History No Total Regenerations Displays the number of regenerations since the last time Service Settings mode was entered Value resets to 0 once the number is viewed 0 Total Gallons Displa...

Page 9: ...m 30 psi available for proper backwash 5 Calcite will add additional hardness to water before softening 6 If iron is present in water supply use salt setting 3 or 4 7 If iron is present in the water s...

Page 10: ...tings Mode 3 is NOT recommended for residential use ST Series 3MAQ1 3BAQ1 2 3BEQ1 2 2MXQ1 3MDQ3 2AMQ1 2APQ1 3 4 2AKQ3 2AJQ3 5 Mode 1 Yes Yes Yes Yes No Yes No No No Regeneration Frequency As Required...

Page 11: ...ttings To maintain peak performance of the appliance inspect and clean the brine tank and air check draw tube assembly annually or when sediment is present in the brine tank Modes 1 and 3 Mode 2 Salt...

Page 12: ...C Close the tap Remove Water From Media Tank A Remove the fill plug from the media tank using a 3 4 inch socket B Insert the siphon hose into the fill port C Siphon the water into the bucket down to...

Page 13: ...L x 3 ___ ppm mg L 0 2 ppm mg L x 3 0 6 ppm mg L Sulfur ___ ppm mg L x 5 ___ ppm mg L 1 0 ppm mg L x 5 5 0 ppm mg L Total compensated ppm ___ ppm mg L 9 1 ppm mg L x Gallons per day for one person 75...

Page 14: ...the container when working with potassium permanganate Use care when removing the cover and pouring it into the feeder B Place the cover on the feeder and secure it with the three stainless steel scr...

Page 15: ...4 3 100241828 Drain End Cap and Container No DLFC See Figure 17 1 4 100241865 O Ring 2 5 100242049 Sleeve 2 6 100241807 Fill Plug 1 7 100241870 O Ring 1 8 100242050 O Ring 2 9 100241175 Bypass Valve...

Page 16: ...t draws the brine solution from the Brine Cabinet The small hole in the Injector Nozzle is the one that creates the injection stream that enters the Throat It is important that this hole is round unda...

Page 17: ...the Sensor Housing The cap is then put in place and the self tapping mount ing screw is installed A slot is provided in the cap for the wire to exit The three wire socket connector must be properly in...

Page 18: ...ft that runs through the main drive axle The Drive Gear is attached at the short end and the Magnet Disc at the other end The Slide Cam is assembled inside of the Piston Slide This Cam Shaft should tu...

Page 19: ...e and then using a twisting action insert the Salt Monitor Probe into the housing Monitor Probe into the housing Caution Caution The 3 8 inch locking clip must be installed to prevent air from being d...

Page 20: ...r No electric power at outlet Check power source Make sure outlet is not controlled by a switch Defective transformer Test with volt meter for 12 VAC at control If less than 10 VAC or greater than 14...

Page 21: ...egenerant potassium permanganate 3MAQ1 3BAQ1 2 3BEQ1 2 2MXQ1 3MDQ Max Compensated Hardness gpg g L 90 1 5 90 1 5 90 1 5 110 1 9 904 1 5 Iron ppm 1 ferrous clear water Maximum ferrous iron reduction2 0...

Page 22: ...minimum of 200 ppm TDS 8 When adding media in the field check for proper settings See Water Conditioner Specifications above 9 Rate of flow must be verified at the end of 1 2 inch I D drain line 10 T...

Page 23: ...2022 A O Smith All Rights Reserved 100359102 DOCUMENT NUMBER RevA0123 A O Smith Water Treatment North America Inc...

Reviews: