(13)
(15)
(15)
(14)
(14)
(7) (13)
(6)
Figure 11: Rear view
(11) Design frame (not within scope of delivery)
(12) Supporting ring with pins
(13) Mounting devices for supporting ring
(14) magnetic holding points
(15) Fixtures for design frame
(16) Clamping springs
Dismantling the device
Pull device out of wall box (Figure 12).
The holding force of the clamping springs (16) must be overcome.
Press fixtures for the design frame (15) inwards slightly and remove the
design frame.
(12)
(11)
Figure 12: Dismantling
5.2 Commissioning
system link – Loading the physical address and application software
The device is connected to the KNX bus and auxiliary voltage.
The physical address is only ever assigned for one device. Only one device
can ever be in programming mode.
Switch on bus voltage
Switch on auxiliary voltage.
Press programming button
(5) at the back of the device.
The programming LED
(5) lights up.
Or via the menu:
Press control surface
Mo. 30.06.14
07:22
Seite 5
Seite 6
Seite 7
in the top display row (8).
The display changes to the menu
.
Then select
-
-
in succession.
Switch control surface for
–
ON
.
The device is in programming mode.
Load the physical address into the device.
The programming LED goes out. In the display, the message
appears briefly. The device is restarted
automatically.
Load application software into the device.
Stick enclosed stickers on the back of the device and note down the physi-
cal address.