Step 1
Cabinet /
Back Plate
Installation
Step 2
Connecting the
power section
Step 3
COMMAND /
CONTROL
terminal
connections
Step 4
Power SUPPLY
and
controller
terminal
connections
Step 5
Check
Step 6
Programming
Step 7A
AUT Mode
(Automatic
Control)
Step 7B
AUT Mode
(Remote
Control)
Step 7C
Emergency
Manual
Operation
Step 7D
Padlocking
5. Check
In manual mode,
check the wiring.
If OK power up
the product
LED Green =
“Power” : ON
LED Red =
“Manuel/Defaut”: ON
6LE007764Aa
Preliminary operations
Check the following upon delivery and after removal
of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and fixing clip
- 1 x quick start instruction sheet
Accessories
• Bridging bars and connection kits
• Terminal shrouds
• Terminal shield
• Voltage sensing kit
• Sealable cover
This quick start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the hager website.
• This product must always be installed and
commissioned by qualified and approved
personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables
connected to the product when voltage may be,
or may become present on the product, directly
through the mains or indirectly through external
circuits.
• Always use an appropriate voltage detection
device to confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
• For 800 – 3200A (Uimp = 12kV). Terminations
must respect a minimum of 14mm clearance
from live parts to parts intended to be earthed
and between poles.
Failure to observe good enginering practises as
well as to follow these safety instructions may
expose the user and others to serious injury or
death.
Installation and commissioning
z
Motorised changeover switch
800A - 3200A
1 Preferred source 2 Alternate source
&
Position 0 order
é
Position 1 order
"
Position 2 order
'
Zero position priority order
(
Remote Control Enable (Priority over Auto)
§
Product Available output (Motor)
è
Position II aux contact
!
Position I aux contact
ç
Position 0 aux contact
a
O/P to HZI910 remote display
z
Product available output (ATS)
e
I/P Inhibition of the ATS controls
r
I/P Manual retransfer
t
S2 Stability Time Bypass: 2AT
y
Priority to TEST ON LOAD: TON
u
TEST OFF LOAD Signal: TOF
i
TEST ON LOAD Signal: TON
o
Not used
p
Contact “Start/Stop Genset”: if S1
is not available the NC contact le
contact (71-72) is close
q
Contact “Start/Stop Genset”: if S1
is not available the NO contact le
contact (71-74) is open
s
Voltage Sensing Inputs
d
Power Supply Inputs
f
Option module slots 1 to 4
Example: control wiring for a 400VAC application having a 3 phase and neutral supply
4. Power supply, sensing and control wiring
Use cables with 1,5 to 2,5 mm
2
section.
Screw M3
Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
Recommanded to use
the voltage sensing kit
ATS Power Supply input II
Power Supply II - L
Power Supply II - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
600 VAC (ph-ph) max
S II - Neutral
332 VAC (ph-n) max
ATS Module Control Inputs
(Fixed)
Contact
Genset Start/Stop
(Product available)
Signal
ATS Power Supply input I
Power Supply II - L
Power Supply II - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing input
Source supply II
S I - Phase 1
S I - Phase 2
S I - Phase 3
600 VAC (ph-ph) max
S I - Neutral
332 VAC (ph-n) max
ATS Module Control Inputs
(Fixed)
ATS Module Output Contact
(Product available)
Remote interface
RJ45 - to HZI910
2
10
4103
312 313 314 315 316 317 63A64A 24 14 04 13
RJ
10
2101
10
5
10
6
41
4413
41
5
41
6
41
7
64
B63B
72
20
1
71
202
20
5206
20
4
20
3
21
0
20
9
20
8
20
7
74
1
F1
F2
L1
L2
L3
N
L1
L2
L3
N
HZI910
Clip
for storage
of the
emergency
handle
4.
3.
3. CONTROL/COMMAND terminals
Ensure that the product is in Manual Mode.
Orientation
Recommended
OK
OK
NO
Dimensions in mm
Door cut-out for front panel
T
250
C
21
28
0
C
21
25
0
M
T
51,5
M
51.5
2000A to 3200A
800A to 1600A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4P
M
335
467
T
80
120
C
391
523
33
8.5
8.5
50
33
10
ø 9
ø 15
800A to 1000A
16 x 11
60
28.5
15.75
15.75
28.5
15
1250A
15
5
5
12.5
25
25
30
30
45
45
90
ø12.5
1600A to 3200A
1. Installation
2. Power terminal connections
Use terminal lugs, rigid or flexible busbars.
800 A
1000 A 1250 A
1600 A
2000 A
2500 A
3200 A
Minimum Cu
cable section
at Ith
(mm
2
)
2 x 185
-
Minimum Cu
busbar section
at Ith
(mm
2
)
2x50x5 2x63x5
2x63x7
2 x 100 x 5 3x100x5 2x100x10 3x100x10
Maximum Cu
cable section (mm
2
)
4 x 185
6 x 185
-
Maximum Cu
busbar width
(mm)
63
100
Type of screw
M8
M10
M12
Recommended
tightening
torque
(N.m)
8,3
20
40
Maximum
tightening
torque
(N.m)
13
26
45
Risk of electrocution, burns or injury to
persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or
damaged in any way it is recommended
to replace the complete product.
.
Ensure that the product is
installed on a flat rigid surface.
HIC4xxG
6LE007764Aa
1
6LE007764Aa
2
6LE007764Aa
3
Slot for optional modules