background image

Step 1

Cabinet /

Back Plate

Installation

 

Step 2

Connecting the

power section

 

Step 3

COMMAND /

CONTROL 

terminal

connections

 

Step 4

Power SUPPLY 

and

controller

terminal

connections

 

Step 5

Check

   

Step 6

Programming

   

  Step 7A

 

AUT Mode

(Automatic 

Control)

  Step 7B

 

AUT Mode 

(Remote 

Control)

  Step 7C

 

Emergency

Manual

Operation

  Step 7D

 

Padlocking

5. Check

In manual mode,  

check the wiring.

If OK power up

the product

LED Green =  

“Power” : ON

LED Red = 

“Manuel/Defaut”: ON

6LE007764Aa

Preliminary operations

Check the following upon delivery and after removal 

of the packaging:

•  Packaging and contents are in good condition.
• The product reference corresponds to the order.

•  Contents should include: 

 

- 1 x motorised changeover switch 

- 1 x emergency handle and fixing clip

 

- 1 x quick start instruction sheet

Accessories

•  Bridging bars and connection kits
•  Terminal shrouds
•  Terminal shield
•  Voltage sensing kit
•  Sealable cover

This quick start is intended for personnel trained in 

the installation and commissioning of this product. 

For further details refer to the product instruction 

manual available on the hager website.
•  This product must always be installed and 

commissioned by qualified and approved 

personnel.

•  Maintenance and servicing operations should be 

performed by trained and authorised personnel.

•  Do not handle any control or power cables 

connected to the product when voltage may be, 

or may become present on the product, directly 

through the mains or indirectly through external 

circuits.

•  Always use an appropriate voltage detection 

device to confirm the absence of voltage.

•  Ensure that no metal objects are allowed to fall 

in the cabinet (risk of electrical arcing).

•  For 800 – 3200A (Uimp = 12kV). Terminations 

must respect a minimum of 14mm clearance 

from live parts to parts intended to be earthed 

and between poles.

Failure to observe good enginering practises as 
well as to follow these safety instructions may 
expose the user and others to serious injury or 
death.

Installation and commissioning

z

Motorised changeover switch 

800A - 3200A

1  Preferred source       2  Alternate source

&

 Position 0 order

é

 

 

Position 1 order

"

 Position 2 order

'

 Zero position priority order

(

 Remote Control Enable (Priority over Auto)

§

 Product Available output (Motor)

è

 Position II aux contact

!

 Position I aux contact

ç

 Position 0 aux contact

a

 O/P to HZI910 remote display

z

 Product available output (ATS)

e

 I/P Inhibition of the ATS controls

r

 I/P Manual retransfer

t

  S2 Stability Time Bypass: 2AT

y

  Priority to TEST ON LOAD: TON

u

  TEST OFF LOAD Signal: TOF

i

  TEST ON LOAD Signal: TON

o

  Not used

p

  Contact “Start/Stop Genset”: if S1

 

is not available the NC contact le 

 

contact (71-72) is close

q

  Contact “Start/Stop Genset”: if S1

 

is not available the NO contact le

 

contact (71-74) is open

s

  Voltage Sensing Inputs

d

  Power Supply Inputs

f

  Option module slots 1 to 4

Example: control wiring for a 400VAC application having a 3 phase and neutral supply

4. Power supply, sensing and control wiring

Use cables with 1,5 to 2,5 mm

2

 section.

Screw M3

Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm

Recommanded to use 

the voltage sensing kit

ATS Power Supply input II

Power Supply II - L

Power Supply II - N

208-277 VAC ±20%:

50/60 Hz

ATS Voltage Sensing input 

Source supply II

S II - Phase 1
S II - Phase 2
S II - Phase 3

600 VAC (ph-ph) max

S II - Neutral

332 VAC (ph-n) max

 ATS Module Control Inputs

 

(Fixed)

Contact 

Genset Start/Stop  

(Product available)

Signal

ATS Power Supply input I

Power Supply II - L

Power Supply II - N
208-277 VAC ±20%:

50/60 Hz

ATS Voltage Sensing input 

Source supply II

S I - Phase 1

S I - Phase 2

S I - Phase 3

600 VAC (ph-ph) max

S I - Neutral

332 VAC (ph-n) max

ATS Module Control Inputs

 

(Fixed)

ATS Module Output Contact

(Product available)

Remote interface

RJ45 - to HZI910

2

10

4103

312 313 314 315 316 317 63A64A 24 14 04 13

RJ

10

2101

10

5

10

6

41

4413

41

5

41

6

41

7

64

B63B

72

20

1

71

202

20

5206

20

4

20

3

21

0

20

9

20

8

20

7

74

1

F1

F2

L1

L2

L3

N

L1

L2

L3

N

HZI910

Clip

for storage

of the

emergency

handle

4.

3.

3. CONTROL/COMMAND terminals

Ensure that the product is in Manual Mode.

Orientation

Recommended

OK

OK

NO

Dimensions in mm

Door cut-out for front panel

T

250

C

21

28

0

C

21

25

0

M

T

51,5

M

51.5

2000A to 3200A

800A to 1600A

800A

1000A

1250A

1600A

2000A

2500A

3200A

4P

M

335

467

T

80

120

C

391

523

33

8.5

8.5

50

33

10

ø 9

ø 15

800A to 1000A

16 x 11

60

28.5

15.75

15.75

28.5
15

1250A

15

5

5

12.5

25

25

30

30

45

45

90

ø12.5

1600A to 3200A

1. Installation

2. Power terminal connections

Use terminal lugs, rigid or flexible busbars.

800 A

1000 A 1250 A

1600 A

2000 A

2500 A

3200 A

Minimum Cu 

cable section 

at Ith

(mm

2

)

2 x 185

-

Minimum Cu 

busbar section 

at Ith

(mm

2

)

2x50x5  2x63x5

2x63x7

2 x 100 x 5  3x100x5 2x100x10 3x100x10

Maximum Cu 

cable section (mm

2

)

4 x 185

6 x 185

-

Maximum Cu 

busbar width

(mm)

63

100

Type of screw

M8

M10

M12

Recommended 

tightening 

torque

(N.m)

8,3

20

40

Maximum 

tightening 

torque

(N.m)

13

26

45

Risk of electrocution, burns or injury to 

persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or 

damaged in any way it is recommended 

to replace the complete product.

.

Ensure that the product is 

installed on a flat rigid surface.

HIC4xxG

6LE007764Aa

1

6LE007764Aa

2

6LE007764Aa

3

Slot for optional modules