10
We reserve the right to make changes of a technical nature
Technical data
Protection classes
-
IP44 with door (plain, transparent or multimedia non-slotted) and IPx4 standard lock FZ598N
-
IP43 with door (plain, transparent or multimedia non-slotted) and IPx3 lock FZ598
-
IP31 with door (slotted, or multimedia slotted)
-
IP30 without door with covered internal panels. IP30 without door from factory is only ensured when
distribution panels are inside.
Note:
-
Take note of the protection class of the equipment.
Impact protection
-
IK09 all around with plain door, except flange (excluded in the Standards)
-
IK07 for slotted, transparent or multimedia door
-
IK05 for cabinet with internal system, without door
Colour
-
Door, exterior walls, covers and internal insulation: RAL 9010 (pure white)
-
Metal parts of the internal system: grey and hot-galvanised
-
univers Z fixing towers: black
Equipment
-
Door and cabinet walls:
-
Made of steel, 1 mm thickness
-
Powder-coated with epoxy polyester paint, burnt in
-
Insulating parts material:
-
Polystyrene (PS): covers, top / bottom parts, rear, sides
-
Polycarbonate / Acrylester-Styrol-Acrylnitril (PC / ASA): corners, multimedia plate
-
Polycarbonate (PC): multimedia door inserts
-
Acrylnitril-Butadien-Styrol (ABS): sealing plug
-
univers Z mounting towers material:
-
Polyamide 6 (PA6): bottom parts, double towers
-
Polycarbonate (PC): top parts
-
Blue seal made from Ethylene-Propylene-Dien (EPDM)
-
Mounting rails and DIN rails made from hot-galvanised steel, 1 mm thickness
-
Multimedia steel beams (patch panels) made from hot-galvanised steel, 1.5 mm thickness
-
Multimedia perforated metal plates made from hot-galvanised steel, 1 mm thickness
Plastic parts in direct contact with the area behind the wall, e.g. corners and top and bottom parts pass the
heat filament test at 750 °C. The cabinet is therefore unsuitable for hollow wall application (850 °C required).
Summary of standards and regulations
-
Tested in accordance with EN 61439 -1/-3 (VDE 0660-600 -1/-3)
-
Dimensions in accordance with DIN 43780
-
IP44 degree of protection in accordance with VDE 0470, part 1 (DIN EN 60529)
-
Protection class IP3X with open or without door
-
Clearance and creepage distance in accordance with VDE 0110, part 1 and 2/1.89
-
Rated isolation voltage: AC 400 V
-
Overvoltage category III
-
Pollution degree 2
-
Insulation material class I
-
Unsuitable for hollow wall application