EG403E

Product Presentation

Presentation

Product delivered with current time and date set.

Automatic change of summer/winter time.

Programming key

-

For permanent overrides

-

For program copy or save

300 programme steps ; ON, OFF, pulses

or

.

Permanent overrides On or Off (

permanent light on).

Temporary overrides On or Off (

flashing).

Overrides (temporary, permanent or time delayed) remote activation possible.

Simulation of presence

.

Keyboard lock function

by PIN number.

Counter of operating time on every output.

Programmable with power off.

Display with backlight.

Technical specifications

Electrical characteristics

• Supply voltage

230 V

+

10/-15%

• Frequency

50/60 Hz

• Power consumption

< 2 VA

• Output

2 changeover

+

2 NO contacts

• Maximum load

AC1

µ 10A 250 V

~

Incandescent lighting:

1500 W

Halogen lighting

Compensated fluorescent tubes //

(max. 45 µF)

400 W

Non compensated fluorescent tubes,

compensated in series

1000 W

Compact fluorescent lamps

400 W

• Minimum load

AC1

100 mA

250 V

~

• Galvanic insulation between power supply and

output

< 4 kV

Rated impulse voltage

4 kV

Functional characteristics

• Programming capacity

300 steps

• Minimum time between 2 steps

1 minute

• Running accuracy

± 0,2 sec/ 24h

• Operating reserve lithium battery, total of 5

years autonomy (unlimited programme backup)

• The product is set into standby state (display

switched-off) after 1 minute with power off.

It switches back into automatic mode as soon

as power is back on or when pressing any key.

• Protection degree

IP 20 / IK 04

Action type

1B

Degree of pollution

2

Software class

A

Environment

• Operating temperature

-10 °C to

+

50 °C

• Storage temperature

-20 °C to

+

70 °C

Temperature for the ball pressure Test

75° to 125°C

Connection by quick-connect terminals

• Flexible

0,75 to 2,5 mm

2

• Rigid

0,75 to 2,5 mm

2

Standards

60730-1

60730-2-7



EG001

§

Warranty

NOT APPLICABLE FOR AUSTRALIA

A warranty period of 24 months is offered on hager

products, from date of manufacture, relating to any material

of manufacturing defect. If any product is found to be

defective it must be returned via the installer and supplier

(wholesaler). The warranty is withdrawn if:

- after inspection by hager quality control dept the device is

found to have been installed in a manner which is contrary

to IEE wiring regulations and accepted practice within the

industry at the time of installation.

- The procedure for the return of goods has not been

followed. Explanation of defect must be included when

returning goods.

This device must be installed only by

a qualified electrician according to the

installation standards in force in the

country.

Usable in all Europe

å

and in Switzerland

Reviews: