1
6E 6354E
C
A
B
1 3 5
2 4 6 8 10 12 14 16
D
11 13 15
7 9
L
N
EG403E
Input for external override
Option
Connection diagram
6E
63
54
E
§
4 channel programmer
weekly cycle with
programming key
User instructions
Navigation &
value setting
Validation
Enter in PROGRAMME mode &
return to previous step
Selection of days of the week
1 = Monday, 2 = Tuesday
... 7 = Sunday.
Canal B command
Canal C command
Canal D command
Canal A command
DCF Antenna (option)
Keyboard locked by PIN code
menu
+
ok
EG403E
Product Presentation
Presentation
⦁
Product delivered with current time and date set.
⦁
Automatic change of summer/winter time.
⦁
Programming key
-
For permanent overrides
-
For program copy or save
⦁
300 programme steps ; ON, OFF, pulses
or
.
⦁
Permanent overrides On or Off (
permanent light on).
⦁
Temporary overrides On or Off (
flashing).
⦁
Overrides (temporary, permanent or time delayed) remote activation possible.
⦁
Simulation of presence
.
⦁
Keyboard lock function
by PIN number.
⦁
Counter of operating time on every output.
⦁
Programmable with power off.
⦁
Display with backlight.
Technical specifications
Electrical characteristics
• Supply voltage
230 V
+
10/-15%
• Frequency
50/60 Hz
• Power consumption
< 2 VA
• Output
2 changeover
+
2 NO contacts
• Maximum load
AC1
µ 10A 250 V
~
Incandescent lighting:
1500 W
Halogen lighting
Compensated fluorescent tubes //
(max. 45 µF)
400 W
Non compensated fluorescent tubes,
compensated in series
1000 W
Compact fluorescent lamps
400 W
• Minimum load
AC1
100 mA
250 V
~
• Galvanic insulation between power supply and
output
< 4 kV
•
Rated impulse voltage
4 kV
Functional characteristics
• Programming capacity
300 steps
• Minimum time between 2 steps
1 minute
• Running accuracy
± 0,2 sec/ 24h
• Operating reserve lithium battery, total of 5
years autonomy (unlimited programme backup)
• The product is set into standby state (display
switched-off) after 1 minute with power off.
It switches back into automatic mode as soon
as power is back on or when pressing any key.
• Protection degree
IP 20 / IK 04
•
Action type
1B
•
Degree of pollution
2
•
Software class
A
Environment
• Operating temperature
-10 °C to
+
50 °C
• Storage temperature
-20 °C to
+
70 °C
•
Temperature for the ball pressure Test
75° to 125°C
Connection by quick-connect terminals
• Flexible
0,75 to 2,5 mm
2
• Rigid
0,75 to 2,5 mm
2
Standards
60730-1
60730-2-7
EG001
§
Warranty
NOT APPLICABLE FOR AUSTRALIA
A warranty period of 24 months is offered on hager
products, from date of manufacture, relating to any material
of manufacturing defect. If any product is found to be
defective it must be returned via the installer and supplier
(wholesaler). The warranty is withdrawn if:
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary
to IEE wiring regulations and accepted practice within the
industry at the time of installation.
- The procedure for the return of goods has not been
followed. Explanation of defect must be included when
returning goods.
This device must be installed only by
a qualified electrician according to the
installation standards in force in the
country.
Usable in all Europe
å
and in Switzerland